STARTING THE GENERATOR SET.
Up
TM-5-6115-465-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Load Connections for Parallel Operation.

TM 5-6115-465-12
TO 35C2-3-446-1
NAVFAC-P-8-625-12
TM 06858B/06859D-12
b. Stopping by Safety Devices.
(11) Depress the fault
location indicator, TEST OR RESET
NOTE
switch and check that all fault
location indicator lights
If any emergency situation
illuminate.
requires continued operation of
the generator set, the BATTLE
(12) On tactical utility
SHORT switch may be used to
generator sets, pull the manual
over-ride any of the safety
speed control all the way out and
devices except the over-speed
then push it in approximately half
and short circuit devices.
way.
The generator set is equipped
b.  Starting.  Refer to figure
with safety devices which will
2-8 for starting instructions.
automatically stop the engine and
After starting, close control
simultaneously open the main load
access door.
contactor upon the occurrence of
engine overheating, loss of engine
STOPPING THE GENERATOR SET.
oil pressure, engine over-speeding,
generator over-voltage, or no fuel.
a.
Normal Stopping.
The occurrence of short circuits,
overloads, generator under voltage,
(1) Refer to figure 2-9 for
generator under frequency, or
stopping procedures.
reverse power will result in the
actuation of a protective device
(2) Refer to table 3-1 and
circuit which will automatically
perform the AFTER OPERATION checks
open the main load contactor, but
and services.
will not stop the engine. The
WARNING
actuation of any protective device
will result in the illumination of
the corresponding indicator light
If acoustic suppression kit is
on the fault indicator panel.
installed, do not allow
Actuation ratings for each of the
personnel to open or close
protective devices is given in the
exhaust discharge door when unit
tabulated data portion of paragraph
iS hot.  Serious burns or
1-6.
personal injury may result.
OPERATION OF TACTICAL
NOTE
PRECISE GENERATOR SETS.
If acoustic suppression kit is
a.  General.  This paragraph
installed. after unit has
provides single unit and parallel
cooled, close both inlet and
operation for both the 50/60 Hz and
discharge doors on roof.
400 Hz tactical precise generator
sets.
b.
Single Unit Operation.
(1) Refer to paragraph 2-10
and start the engine.
2-13