Table 2-2. Generator Set Troubleshooting (Cont)
Up
TM-5-6115-545-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Table 2-2. Generator Set Troubleshooting (Cont)

Table 2-2. Generator Set Troubleshooting (Cont) Malfunction Probable  cause Corrective action 27. Generator runs at 130 a. Defective overload a. Replace  K14  (para  8-6 percent  or  more relay (K14). and 8-7). rated current for longer than 10 minutes, b. Defective re- b. Replace resistor R23, R24 or CB2 does not open and sisters  R23,  R24 R25, if ohmmeter test indi- overload  indicator  does or R25. cates defect (fig. 8-2 and 8-3). not light. c. Defective   current c. Replace   defective   current’ transformer  CT1, transformer  CT1,  CT2  or CT2 or CT3. CT3  (para  6-7  thru  6-8). 28. Generator runs at Defective overvoltage Replace overvoltage relay (para 8-6 overvoltage  (130 relay  K2. and 8-7). percent.    Set does not shut down and overvoltage  indi- cator  does  not  light. 29. Generator runs Defective undervoltage Replace undervoltage relay K11 under voltage (85 percent relay  Kilo (para 8-6 and 8-7). of rated voltage or less). CB2 does not open and undervoltage   indicator does not light (Class  I  only) 30. Percent power meter Reverse power relay Measure  dc  voltage  at  K15  terminals reads down scale with (K15)   defective. 3 and 4. It should be 24 volts 2 or more sets paral- (positive on terminal 3). Check leled. for Vdc at pins 1 and 2. If 2 or more Vdc are present with 1 positive replace reverse power relay (para 8-6 and 8-7). 31. Set starts but will not a. System  fault  as a. Correct indicated fault. run  unless  protection indicated by bypass  switch  (S7) fault  indicator is  closed. panel. b. If no lamp is il- b. Replace any defective lamps. luminated,  press fault  indicator test  switch  to ensure  that  all lamps  are  working. NOTE If the corrective action in a and b above does not correct the malfunction, proceed to determine if one of the fol- lowing components are defective by placing jumpers across their contacts as follows: c. Overvoltage c. Terminals 3 and 4 of K2. relay  K2. d. Low oil pressure d. Terminal 3 of K2 and 4 of AS. switch OP and high coolant  temperature switch WT. Change 5 2-17