POWER DISTRIBUTION UNIT - continued
Up
TM-3-4240-302-30-P-5 Power Distribution Unit (NSN 4240-01-068-8645) Manual
Next
POWER DISTRIBUTION UNIT - continued

TM 3-4240-302-30&P-5
LOCATION
ITEM
ACTION
REMOVAL
Panel
DUST FAN circuit
1.
Remove six screws (1), washers (2), and wires
breaker CB4
(3) from circuit breaker CB4 (4). Tag wires.
2.
Unsolder and tag wires from A3 and A4
contacts on circuit breaker CB4 (4).
3.
Unscrew boot (5), and remove circuit breaker
CB4 (4) from panel (6).
INSTALLATION
1.
Insert circuit breaker (4) in panel (6), and
secure with boot (5).
2.
Solder wires to A3 and A4 contacts of circuit
breaker. Refer to wiring diagram (p. 2-39).
3.
Install wires (3) on six electrical terminals using
six screws (1) and washers (2). Refer to wiring
diagram (p. 2-39).