Power Output, Regulation, and Ripple Tests at 220-Volt Input
Up
TM-11-6130-243-35-1 Power Supply PP-4606A/G Manual
Next
Figure 3­1. Connection diagram for power output, regulation, and ripple tests at 220-volt input.

TM 11­6130­243­35­1
c. Procedure.
3­5. Insulation Resistance Test
(1) Connect the ZM-21A/U ground lead
a. Test Equipment. The only test equipment
to the PP-4606A/G frame.
required is Ohmmeter ZM-21A/U.
(2) Connect the ZM-21A/U line lead to
b. Test Connections and Conditions. This
any terminal of the primary wind-
test is performed with the PP-4606A/G dis-
ings of T1, T2, and T3.
connected from the ac power source, and is
used to check the insulation resistance of the
(3) Operate the ZM-21A/U and observe
primary windings of power transformers T1,
t h e indication on the ZM-21A/U
meter. The PP-4606A/U meets the
T2, and T3. The test is written for the PP-
performance standard if the ZM-21
4606A/G connected for 220-volt ac operation.