Section IV. REMARKS
Up
TM-11-6130-243-14-3 Power Supply PP-4606C/G (NSN6130-00-504-0327) Manual

TM 11­6130-243-14-3
WARNING
PRIOR TO INSTALLATION
A shock hazard, due to incorrect wiring, may exist within
some  PP-4606C/U  (NSN  6130-00-504-0327)  units  manufactured
by MCL, Inc, under contract number DAAB07-76-C-1411.
The wiring does not follow the National Electrical Color Code
for power circuits.  Before connecting the unit to an external
ac power source, check that the 100 foot ac power input cable
i s internally wired as shown on this illustration. If unit is
not wired correctly, red tag the unit until the wiring has been
changed.
Figure FO­ 1. Schematic, power supply PP­4606C/G