STATIC VOLTAGE REGULATION TEST - continued
Up
TM-11-5820-765-34 Power Supplies PP-4763/GRC (NSN 5820-00-937-7690) and PP-4763A/GRC (NSN 5820-00-113-9768) Manual
Next
Chapter 3. GENERAL SUPPORT MAINTENANCE

TM 11-5820-765-34
Verifying PP-4763A 230-volt input
The above voltage regulation test was conducted at 115 volts. If a 230-volt, single-phase, 50/60
H z power source is available, test PP-4763A at 230-volt input.
Procedure:
S e t TB-1 ac input links to 230 volts ac.
Connect power cable to 230-volt source.
Repeat test equipment settings, control settings for step 1 of paragraph 2-14 in test chart.
Repeat ripple voltage, dc output voltage checks in step 1 of paragraph 2-14.
2-15. TEST DATA SUMMARY
Summary of performance standards.
Input
PP-4763
115 volts
Voltage
PP-4763A
115 or 230 volts
50/60 Hz
Frequency
Single
Phase
Current
PP-4763
23 amperes
(full load)
PP-4763A
23 amperes at 115-volt input
11.5 amperes at 230-volt input
Output
28-volt
operation
(27-29
volts
dc)
Voltage
50 amperes
Current (full load)
1.0 percent rms
Ripple  Voltage
(maximum)
Voltage
Regulation
Static voltage: *0.5 percent (maximum total voltage
deviation
280
millivolts).