SECTION II.  TROUBLESHOOTING PROCEDURES
Up
TM-5-3610-295-13P-2 Printing Plant Special Warfare Transportable - Press Shelter Manual
Next
Operator Troubleshooting -cont

TM 5-3610-295-13&P-2 3-3.  GENERAL.  - Continued Table 3-1.  Operator Troubleshooting MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION NO ELECTRICAL POWER TO SHELTER SYSTEM. WARNING The  15  KW  generator  must  be  shut  down  or  the  main  circuit  breaker  on  power distribution box must be in the OFF position before connecting main power cable. Failure to do so may result in DEATH or serious injury. When used with the Modular Printing System, to ensure safety of operator, only the Module C supervisor is authorized to operate controls of the power distribution box. CAUTION Connect the primary power cable to the input power receptacle located near the door of the shelter.  The cable connector and the receptacles are keyed to ensure proper connection. Step 1.  Check that the main power cable is correctly connected at main power receptacle. Step 2.  When used with the Modular Printing System, check to see if the main power cable is properly connected at power distribution box.  Request Module C supervisor verify connection and operation of the power distribution box. Step 3.  Inspect to see that the generator is operating properly. Start the 15 KW power plant in accordance with TM 5-6115-464-14&P or TM 5-6115-625-14&P. 2.  NO ELECTRICAL POWER AT EQUIPMENT RECEPTACLES. Step 1.  Check to see if applicable circuit breaker is in the ON position. Set applicable circuit breaker to ON. 3-4

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing