TM 9-4110-256-14
Table 2-1. Preventive Maintenance Checks and Services for Model F1000RE
NOTE
If the equipment must be kept in continuous operation, do only the procedures that can be done
without disturbing operation. Make complete checks and services when the equipment is shut
down.
Location
Item
Interval
Item to
Procedure
Not Fully Mission
No.
Check/Service
Capable If:
Refrigeration
Unit Exterior
1
Before
Thermometer
Thermometer should indicate refrigerator
Thermometer does not
enclosure temperature. If it does not, notify unit
indicate refrigerator
maintenance to replace it.
enclosure temperature.
Refrigeration
Unit Interior
WARNING
High voltage and exposed rotating parts
are contained in the refrigeration unit.
Personal injury can result if power is
connected with doors open.
2
Before
Sight
Inspect sight indicator port for cracks and note
Sight indicator port is
Indicator
center indicator color. If cracked or yellow,
cracked or center indicator
notify direct support maintenance to replace it
color is yellow.
or evacuate the refrigeration system as
necessary.
3
Before
Fan is cracked, torn, or
Inspect for loose connection to fan drive shaft. If
loose.
damaged or loose, notify unit maintenance to
tighten or replace it as necessary.
4
Before
V Belt
Inspect the V belt for frayed edges, cracks,
V belt is frayed, cracked,
glazing, or hard brittle condition. Inspect for
glazed, or hard and
excessive looseness or slippage. If damaged or
brittle. V belt is
loose, notify unit maintenance to tighten or
excessively loose or
replace it as necessary
slipping.
5
Before
Flange
Inspect flange bearings for loose or missing
Flange bearing mounts are
mounting hardware and looseness of fan drive
loose or fan drive shaft is
shaft in bearing. If loose, notify unit
loose in bearing.
maintenance to tighten or replace it as
necessary.
2-8