TROUBLESHOOTING USING GSC FAULT CODES - Continued
SYMPTOM
14.
CID 97 E FMI 01
MALFUNCTION
Derate Overridden.
FMI 01 - Data is Valid but Data is Below Normal Operating Range.
Event Code. Engine derate overridden. Verify presence of fault.
CORRECTIVE ACTION
STEP 1.
Set Battery Disconnect Switch to ON. Set DEAD CRANK SWITCH to NORMAL.
On EMCP turn the ENGINE CONTROL switch to COOL DOWN/STOP.
STEP 2.
Press ALARM CODES on GSC keypad.
STEP 3.
Check for logged fault code, troubleshoot, and correct (WP 0008 and/or
STEP 4.
Verify the problem is resolved.
NOTE
The following failure indicates that GSC is unable to receive valid data about oil pressure from
ECM.
SYMPTOM
15.
CID 100 E FMI 02
MALFUNCTION
Oil Pressure Sensor.
FMI 02 - Erratic, Intermittent, or Incorrect Signal.
CORRECTIVE ACTION
STEP 1.
On EMCP, turn ENGINE CONTROL switch to OFF/RESET. Battery Disconnect
switch is OFF, DEAD CRANK SWITCH is OFF.
STEP 2.
Inspect connectors ENG-P2 on the engine harness (FO-2, sheet 1) and P1 on
the ECM to EMCP Harness (FO-2, sheet 2).
STEP 3.
Conduct an appropriate pull test on wires in the ENG-P2 and ENG-P1 connectors
to ensure wires are tight and secure.
STEP 4.
Disconnect ENG-P2 from ECM J2, ENG-P201 from the oil pressure sensor, and
ENG-P202 from the fuel pressure sensor. Verify continuity from ENG-P201-A to
ENG-P202-A and ENG-P2-2. Verify continuity from ENG-P201-B to ENG-P202-
B and ENG-P2-3. Verify continuity from ENG-P201-C to ENG-P2-24.
STEP 5.
Check the wires on both ENG-P1 and ENG-P2 harnesses for abrasion and pinch
STEP 6.
If necessary, repair and/or replace the connectors and/or wiring (WP 0088).