Section V.  PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)
Up
TM-5-6115-612-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 600 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Table 4-1. Preventive Maintenance Checks and Services

ARMY   TM5–6115–612–12 NAVY    AG-320B0-0MM-000 4-9.  GENERAL.  (cont) Table  4-1.  Preventive  Maintenance  Checks  and  Services W  -  Weekly  (40  hours) Total   M/H:   1.0 Interval M  -  Monthly  (100  hours) Total   M/H:   7.1 S  -  Semiannual  (500  hours) Total   M/H:   4.3 Organization Work W M S Inspection   procedures M/H 6 7 8 9 10 11 29 30 12 31 13 14 BLEED AIR CONNECTOR AND BLEED AIR LINE Inspect bleed air line connector and bleed air line in accordance with  paragraphs  4-18a  and  4-19a. GECM WIRING HARNESSES Inspect  GECM  wiring  harnesses  in  accordance  with  paragraph  4-28a SLAVE RECEPTACLE Inspect  slave  receptacle  for  damage. GENERATOR ELECTRONIC CONTROL MODULE (GECM) Inspect GECM for damage and loose connections. CIRCUIT BREAKER Inspect  circuit  breaker  for  damage  and  proper  operation. ELECTRICAL FUEL TRANSFER PUMP Inspect  and  service  electrical  fuel  transfer  pump  in  accordance  with paragraphs  4-37a,  4-37b  and  4-37c. Test  semiannually  in  accordance  with  paragraph  4-37a. PRIMARY FUEL (FLUID) FILTER Change  filter  element  in  accordance  with  paragraph  4-38a. ENGINE FUEL TANK Inspect  engine  fuel  tank  in  accordance  with  paragraph  3-9b. SECONDARY FUEL (FLUID) FILTER Change  filter  element  (paragraph  4-40). SOLENOID VALVE Inspect  valve  in  accordance  with  paragraph  3-9. FUEL INJECTION NOZZLES Inspect  atomizers  in  accordance  with  paragraph  4-43. 0.1 0.1 0.1 0.1 0.1 0.4 0.5 0.2 0.2 0.1 0.2 2.5 Change 2 4-17