DIESEL TEST PROCEDURE
Up
TM-10-6640-222-13P Emcee Micro-Separometer Mark V Deluxe Model No. 1140 Manual
Next
FILTER SEPARATOR MONITOR TEST

MICRO-SEPAROMETER MARK V DELUXE OPERATION MANUAL 12.9 When securely in place depress the "START" pushbutton.  This will initiate the automatic program. AUTOMATIC PROGRAM Pulsed Tone 4 Seconds Meter Adjust Period #1 10 Seconds Emulsification 30 Seconds Wait 30 Seconds Pulsed Tone 4 Seconds Meter Adjust Period #2 10 Seconds Syringe Drive Down 45 Seconds Wait 56 Seconds Steady Tone 4 Seconds Meter Read 10 Seconds 12.9.1 The automatic program starts with a read meter warning followed by a 10 second full scale adjustment period. During this period adjust the display to 100 using the meter adjust up or down switches. 12.9.2 After the emulsification period, remove the syringe from the emulsifier and insert the plunger with the help of the wire aid.  Remove the plug from the bottom, replace it with an ALUMICEL®   COALESCER marked DIESEL, and place the whole assembly onto the syringe drive mechanism.  Attach ground lead between ground jack on side of syringe drive and ALUMICEL®   COALESCER.  Place a waste container beneath the syringe to collect the unwanted fuel. 12.9.3 At the end of the second meter adjust period the syringe will start down.  Remove and empty the sample vial and prepare for sample collection.  The audio alert and the C/S indicator will indicate the proper time to collect the last 15 milliliters from the syringe. 12.9.4 Place the sample vial in the turbidimeter and rotate to the marked position. 12.9.5 When the steady tone starts the meter will automatically turn on.  An additional one second tone during the meter on period will indicate the proper time to read the meter.  Record the reading and report as Micro-Separometer rating (DMSEP rating). COPYRIGHT 1984 EMCEE ELECTRONICS, INC. REVISION DATE:  FEBRUARY 12, 1987 PAGE 14

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing