Figure 4   Level Control Valve
Up
Engineering Symbology Prints and Drawings Volume 1 of 2
Next
Piping  Systems

DOE-HDBK-1016/1-93 ENGINEERING FLUIDS DIAGRAMS AND PRINTS Engineering Fluid Diagrams and Prints Figure 5   Control Valves with Valve Positioners In Example A of Figure 5, the reader can reasonably assume that opening of the control valve is  in  some  way  proportional  to  the  level  it  controls  and  that  the  solenoid  valve  provides  an override of the automatic control signals.  However, the reader cannot ascertain whether it opens or closes the control valve.  Also, the reader cannot determine in which direction the valve moves in response to a change in the control parameter.  In Example B of Figure 5, the reader can make the same general assumptions as in Example A, except the control signal is unknown.   Without additional information, the reader can only assume the air supply provides both the control signal and  motive  force  for  positioning  the  control  valve.    Even  when  valves  are  equipped  with positioners, the positioner symbol may appear only on detailed system diagrams.  Larger, overall system  diagrams  usually  do  not  show  this  much  detail  and  may  only  show  the  examples  of Figure 5 as air-operated valves with no special features. Control  Valve  Designations Figure 6   Control Valve Designations A  control  valve  may  serve  any  number  of  functions  within  a  fluid  system.    To  differentiate between valve uses, a balloon labeling system is used to identify the function of a control valve, as shown in Figure 6.   The common convention is that the first letter used in the valve designator indicates  the  parameter  to  be  controlled  by  the valve.   For example: F = flow T = temperature L = level P = pressure H = hand (manually operated valve) The second letter is  usually a "C" and identifies the valve as a controller, or active component, as opposed  to  a  hand-operated  valve.     The  third letter   is   a   "V"   to   indicate   that   the   piece   of equipment is a valve. PR-02 Rev. 0 Page 6

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing