Figure 16   Proportional Temperature Control System
Up
Instrumentation and Control 2 of 2
Next
Figure 18   Controller Characteristic Curve

Process Controls PROPORTIONAL CONTROL SYSTEMS Steam is admitted to the heat exchanger to raise the temperature of the cold water supply.   The temperature detector monitors the hot water outlet and produces a 3 to 15 psi output signal that represents a controlled variable range of 100o to 300oF.   The controller compares the measured variable signal with the setpoint and sends a 3 to 15 psi output to the final control element, which is a 3-in control valve. The  controller  has  been  set  for  a  proportional  band  of  50%.   Therefore,  a  50%  change  in  the 200oF span, or a change of 100oF, causes a 100% controller output change. The proportional controller is reverse-acting so that the control valve throttles down to reduce steam flow as the hot water outlet temperature increases; the control valve will open further to increase steam flow as the water temperature decreases. The combined action of the controller and control valve for different changes in the measured variable is shown in Figure 17. Initially, the measured variable value is equal to 100oF.   The controller has been set so that this Figure 17   Combined Controller and Final Control Element Action value of measured variable corresponds to a 100% output, or 15 psi, which in turn, corresponds to a "full open" control valve position. At  time  t1,  the  measured  variable  increases  by  100oF,  or  50%,  of  the  measured  variable  span. This 50% controller input change causes a 100% controller output change due to the controller’s proportional band of 50%.   The direction of the controller output change is decreasing because the controller is reverse-acting.   The 100% decrease corresponds to a decrease in output for 15 psi to 3 psi, which causes the control valve to go from fully open to fully shut. Rev. 0 Page 25 IC-07