Back System Capacities and Detailed Data on Components (Continued) | Up TM-9-6115-604-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 5 Kw. 1 Phase-2 Wire 1 Phase -3 Wire 3 Phase -4 Wire 120. 120/240 and 120/208 Volts Manual | Next System Capacities and Detailed Data on Components (Continued) |
TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM (CONTINUED)
Switch
Drawing Number:
Rating:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Contacts:
Terminals:
Manufacturer:
Part Numbers:
Number of Poles:
FSCM:
Terminator Elbow
Drawing Number:
Voltage (Maximum):
Withstand:
Voltage Impulse:
AC:
DC:
Minimum Corona:
Continuous Current:
Switching Current:
Fault Closure:
Operating Temperature:
Storage Temperature:
Humidity Conditions:
Manufacturer:
Part Number:
FSCM:
FUEL SYSTEM
Fuel Injectors:
Type:
Flow:
80-7948
120/277 V ac, 15 amperes
-25° to +125°F (-31° to 51°C)
-65° to +155°F (-53° to 68°C)
To 100%
Solid silver, cadmium oxide
Binding head screws suitable for accepting wires up to
No. 10 AWG
Harvey Hubbell
1201
1203
One
3 way
74545
80-7389
8.3 kV rms phase to ground; 14.4 kV rms phase
to phase
95 kV crest, 1.2 x 50 ms wave
60 Hz 1 minute, 34 kV rms
15 minutes, 53 Kv
11 Kv rms
200 A
Per ANSI 386-1977; circuit for 10 switching
operations; 200 A at 14.4 Kv phase to phase
Per ANSI 386-1977; circuit at 14.4 Kv - 10,000 A
rms symmetrical for 10 cycles or 15,000 A at 8.3 Kv
phase to ground rms symmetrical for 4 cycles
(when used with comparably rated bushing)
-25° to +125°F (-31° to 51°C)
-65° to +155°F (-53° to 68°C)
To 100%
RTE Corporation
260459B61 M
96207
PT-Type D
118 cc
1-30
|