Back System Capacities and Detailed Data on Components (Continued) | Up TM-9-6115-604-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 5 Kw. 1 Phase-2 Wire 1 Phase -3 Wire 3 Phase -4 Wire 120. 120/240 and 120/208 Volts Manual | Next System Capacities and Detailed Data on Components (Continued) |
TM 9-6115-604-34
NAVFAC P-8-633-34
Table 1-5. System Capacities and Detailed Data on Components (Continued)
AC ELECTRICAL POWER GENERATION AND CONTROL SYSTEM (CONTINUED)
Overvoltage Relay
Drawing Number:
Nominal Voltage:
Type Sensing:
O/V Adjustment Range:
Factory Setting:
Operating Temperature:
Storage Temperature:
Contact Rating:
Manufacturer:
Part Number:
FSCM:
Crank Timer Relay
Drawing Number:
Nominal Voltage:
Voltage Limits:
Pin 4:
Pin A:
Timing Data:
On Time:
Off Time:
Delay:
Switching Data,
Semiconductor Method:
Pin 7:
Pin 9:
Pin B:
Operating Temperature:
Storage Temperature:
Manufacturer:
Part Number:
FSCM:
Ground Fault Relay
Drawing Number:
Voltage Rating:
Tap Range Volts:
Contacts:
Current Rating:
Operating Temperature:
Storage Temperature:
80-7794
208 V ac, 3 phase, 3 wire, 50/60 Hz
Highest of the 3-phase input
208 to 260 V ac
239 V ac
-25° to +125°F (-31° to 51°C)
-65° to +155°F (-53° to 68°C)
5 amperes at 120 V ac or 28 V dc (resistive)
Wilmar Electronics, Incorporated
301 -38C
25248
80-7658
24 V dc
7 to 30 V dc
24 ± 10% V dc
15 ± 5% seconds
15 ± 5% seconds
Operate 20 ± 5% seconds
100 milliamperes at 12 V dc
200 milliamperes at 12 V dc
100 milliamperes at 12 V dc
-25° to +125°F (-31° to 51°C)
-5° to +155°F (-53° to 68°C)
Dynamics Corporation of America,
Potter and Brumfield
CZ639
89265
80-7436
199 V ac, 10 seconds at 360 V ac
16 minimum, 64 maximum; 50/60 Hz
2 normally open
30 amperes at 250 V dc, 5 amperes continuous
-25° to +125°F (-31° to 51°C)
-65° to +155°F (-53° to 68°C)
1-27
|