Page Title: Figure 1-11. Output Supply System
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

Back
Figure 1-10. Air Intake and Exhaust System
Up
TM-9-6115-464-12 Wrench Impact Hydraulic Model MV-12-140T Manual
Next
Figure   1-12.   Hydraulic   System   Diagram

ARMY  TM  9-6115-464-12 AIR FORCE TO 35C2-3-445-1 NAVY NAVFAC P-8-624-12 1-19 OUTPUT  SUPPLY SYSTEM. The Output Box contains four output terminals (Figure 1-11), L1, L2, L3, L0. Power generated by the generator set is supplied to the output terminals through the voltage reconnection board. The voltage reconnection board allows the generator to supply 120/208 or 240/416 Vac to the output terminals. The CKT BKR switch closes and opens the main load contactor. This enables or interrupts the power output terminals. It selects current in each phase, three line-to-line voltages, and three line-to-neutral voltages which are indicated on the ammeter and voltmeter. Figure  1-11.  Output  Supply  System 1-21