Page Title: Table 1-4. Electrical Performance Characteristic Parameters AC-3% Droop
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

Back
Table 1-3.  Parameters AC-0% Droop
Up
TM-5-6115-593-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 600 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
CHAPTER 2 GENERAL MAINTENANCE INSTRUCTIONS

TM5-6115-593-34 NAVFAC P-8-631-34 TO-35C2-3-463-2 Table 1-4.  Electrical Performance Characteristic Parameters AC-3% Droop TEST METHOD CHARACTERISTIC PARAMETER VALUE MIL-STUD-705 Voltage Characteristics Regulation (%) 2% 608.1 Steady-state-stability (variation) Short term (30 seconds) 1% 608.1 Long term (4 hours) 2% 608.2 Transient performance Application of rated load Dip (%) 20% 619.2 Recovery (seconds) 3 sec 619.2 Rejection of rated load Rise (%) 30% 619.2 Recovery (seconds) no spec 619.2 Waveform Maximum deviation factor (%) 5% 601.1 Maximum individual harmonic (%) 2% 601.4 Voltage unbalance with unbalance load (%) 5% 620.2 (Note 1) Phase balance voltage (%) 1% 508.1 Voltage adjustment range 50 Hz (120/208 volts) 190 to 213 V 50 Hz (240/416 volts) 380 to 426 V 511.1 60 Hz (120/208 volts) 197 to 250 V 60 Hz (240/416 volts) 395 to 500 V 511.1 Frequency Characteristics Regulation (%) 3 608.1 Steady-state-stability (variation) (bandwith %) Short term (30 seconds) .5% 608.1 Long term (4 hours) 1% 608.2 Transient performance Application of 50% of rated load Undershoot (%) 4% 608.1 Recovery (seconds) 4 sec 608.1 Rejection of 50% of rated load Overshoot (%) 4% 608.1 Recovery (seconds) 4 sec 608.1 Frequency adjustment range (Hz) 50 Hz +5% 511.2 60 Hz +4% 511.2 NOTE 1.   The   generator   set   connected   for   three   phase   output   and   supplying   a   single   phase,   unity   power   load connected line-to-line with no other load on the set.  The load current to be 25 percent of the rated full load current of the set. 1-16

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing