TM 5-6115-593-12
TO 35C2-3-463-1
STEP 1. PERFORM STEPS 1 THROUGH 7 OF FIGURE 2-5.
STEP 2. ON THE REMOTE CONTROL MODULE PANEL CHECK ENGINE AND GEN FAULT INDICATORS BY
PLACING ANNUNCIATOR TEST SWITCH IN TEST POSITION TO VERIFY THAT ALL INDICATORS LIGHT.
STEP 3. CHECK VOLTAGE AND FREQUENCY REQUIREMENTS OF THE LOAD AGAINST THE VOLTAGE AND
FREQUENCY CONNECTIONS ON THE SET.
WARNING
MAKE CERTAIN THAT NO TOOLS, PARTS, OR LOOSE ITEMS ARE ON ANY PART OF THE ENGINE
SINCE THEY MIGHT CAUSE BODILY INJURY TO PERSONNEL WHEN THE ENGINE IS STARTED.
Figure 2-15. Preparation for Starting Using Remote Control Module
2-33
|