Order this information in Print

Order this information on CD-ROM

Download in PDF Format

     

Click here to make tpub.com your Home Page

Page Title: CHAPTER 6 MAINTENANCE OF CONTROL SYSTEM
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

Back
Figure  5-14.   Checking Pinion Travel STYLE II Starter
Up
TM-5-6115-585-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 5 KW 1 Phase 2 Wire 1 Phase-3 Wire 3 Phase-4 Wire 120 120/240 and 120/208 Volts Manual
Next
Figure   6-1.   Control   Cubicle   Wiring   Harness

6-1. DC CONTROL SYSTEM. TM5-6115-585-34 NAVFAC  P-8-623-34 TO-35C2-3-455-2 TM-05684C/05685B-34 CHAPTER 6 MAINTENANCE OF CONTROL SYSTEM Section I. DESCRIPTION AND FUNCTION R e f e r    t o    t h e    O p e r a t o r    a n d    O r g a n i z a t i o n al Maintsnance   Manual   for   the   description   and   function of   the   dc   control   system. 6-2. AC INSTRUMENTATION SYSTEM. R e f e r    t o    t h e    O p e r a t o r    a n d    O r g a n i z a t i o n a l Maintenance  Manual  for  description  and  function  of the   ac   instrumentation   system. Section  II. 6-4.  CONTROL  CUBICLE. a.   Wiring   Harness. (1)   Remove.   Disconnect   wires   of   wiring   harness from  all  components.  Remove  clamp  attaching  harness to   control   panel   and   remove   harness. (2)   Repair.    Table   6-1   lists   the   wire   number, gauge,   color,   length   and   terminal   lugs   for   each   wire in   the   harness.   Repair   consists   of   replacing   wires   as required. (3)   Installation.   Install   harness   by   connecting wires  to  components  per  figure  6-1.  Attach  harness  to control  panel  with  clamp. b.   Meters   (on   equipment   test). (1)  Frequency  Meter  (M3)  (16,  figure  6-3).  Con- nect   a   frequency   meter   of   known   accuracy   to   single phase   output   terminals   of   load   terminal   board.   Make certain   reconnection   switch   is   in   proper   position   for single   phase   output.   Operate   Generator   Set   and   check readings  of  panel  meter  (M3)  against  test  frequency meter.  If  panel  meter  does  not  give  the  same  reading as  the  test  meter,  test  transducer  as  given  in  (2)  below. (2)   Frequency   Transducer   (A3)   (56,   figure   6-3). Test   transducer   using   the   same   procedure   as   for testing  frequency  meter.  If  transducer  does  not  give proper   meter   reading,   replace   the   transducer   and/or the   meter. 6-3. VOLTAGE REGULATOR. Excitation   current   is   controlled   through   the   static type   automatic   voltage   regulator.   The   voltage   regu- lator  continuously  compares  the  output  voltage  of  the synchronous   generator   with   a   stable   reference   volt- age.   The   difference   between   the   two   voltages   con- stitutes   an   error   signal   which   indicates   an   output voltage   that   is   higher   or   lower   than   the   generator set   point.   This   error   signal   is   amplified   and   used   to control   the   direct   current   output   of   the   voltage   regu- lator   which   is   applied   to   the   control   windings   of   the current-voltage   transformers. MAINTENANCE (3)  Percent  Current  Meter  (M4)  (17,  figure  6-3). Connect  an  ac  test  ammeter  in  series  with  the  %  rated current   meter.   Operate   Generator   Set   with   a   single phase  load.  Continue  adding  load  to  set  until  meter reads  0.75  amps.  Meter  (M4)  should  read  100%  ±2%. Replace  meter  if  necessary. (4)   AC   Voltmeter   (M5)   (18,   figure   6-3).   Attach test   ac   voltmeter   in   parallel   (across   terminals)   with panel   ac   voltmeter   (M5).   Operate   Generator   Set   and compare   readings   of   the   two   meters.   Panel   voltmeter must  be  accurate  to  ±  2.5%,  except  between  115  and 125   volts,   accuracy   must   be   ±   3   volts   and   between 200  and  250  volts,  accuracy  must  be  ±  5  volts.  If  panel meter   does   not   meet   these   requirements,   replace meter. c.   Meters   (remove). (1)   Frequency   Meter   (M3)   (16,   figure   6-3).   Tag and   disconnect   two   leads   from   meter.   Remove   three screws,   lockwashers,   and   nuts   attaching   meter   to panel   and   remove   meter. (2)   Frequency   Transducer   (A3)   (56,   figure   6-3). Tag  and  disconnect  four  leads  to  frequency  transducer. Remove  four  screws  (54)  and  nuts  (55)  attaching transducer   to   back   of   control   cubicle   and   remove transducer. (3)   Percent   Current   Meter   (M4)   (17,   figure   6-3). Tag   and   disconnect   two   leads   from   meter.   Remove three   screws,   lockwashers,   and   nuts   attaching   meter to   control   panel   and   remove   meter. Change 4 6-1

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing