Figure   4-1.   Uncrating   Generator   Set
Up
TM-5-6115-585-12 Generator Set Diesel Engine Driven Tactical Skid Mtd 5 KW 1 Phase 2 Wire 1 Phase-3 Wire 3 Phase-4 Wire 120 120/240 and 120/208 Volts Manual
Next
Figure   4-2.   Grounding   Generator   Set

ing   flammable   gases   or   vapors.   Use   as   few   bends   in   the pipe   and   as   short   a   pipe   as   possible.   The   exhaust   pipe s h o u l d     i n c l u d e     a     l o w     p o i n t     w i t h     s u i t a b l e     m e a n s     f or draining   of   condensate.   Provide   metal   shields,   12   in- ches   larger   in   diameter   than   the   exhaust   pipe   where   the line    passes    through    flammable    walls.    Wrap    the    exhaust pipe   with   asbestos   if   there   is   any   danger   of   anyone touching   it. Do   not   operate   the   engine   Generator   Set   in   an e n c l o s e d     a r e a     u n l e s s     t h e     e x h a u s t     g a s e s     a re p i p e d     t o     t h e     o u t s i d e .     I n h a l a t i o n     o f     e x h a u s t fumes   will   result   in   serious   illness   or   death. TM5-6115-585-12 NAVFAC    P-8-623-12 TO-35C2-3-455-1 T M - 0 5 6 8 4 C / 0 5 6 8 5 B - 1 2 d .     L e v e l i n g .     T h e     G e n e r a t o r     S e t     i s     a     p o r t a b l e     u n it and   is   designed   to   operate   satisfactorily   up   to   15º   out- of-level.   Set   up   the   unit   as   level.   Set   up   the   unit   as   level a s    p o s s i b l e    a n d    k e e p    i t    a s    l e v e l    a s    p o s s i b l e    d u r i n g o p e r a t i o n. e.   Grounding.   The   Generator   Set   must   be   grounded p r i o r     t o     o p e r a t i o n .     T h e     g r o u n d     c a n     b e ,     i n     o r d e r     of preference:   (1)   an   underground   metallic   water   piping system,   (2)   a   driven   metal   rod,   or   (3)   a   buried   metal plate   (figure   4-2).   If   the   effectively   grounded   portion   of the   buried   metallic   water   pipe   is   less   than   10   feet   due   to insulated    sections    or    joints,    this    preferred    grounding method   must   be   supplemented   by   an   additional   driven metal   rod   ground   or   a   buried   metal   plate   ground.   A d r i v e n    m e t a l    g r o u n d    r o d    m u s t    h a v e    a    m i n i m um diameter   of   5/8   inch   if   solid   or   3/4   if   pipe,   and   driven to   a   minimum   depth   of   8   feet.   A   buried   metal   ground p l a t e     m u s t     h a v e     a     m i n i m u m     a r e a     o f     9     s q u a r e     f e e t, m i n i m u m    t h i c k n e s s    o f    1 / 4    i n c h ,    a n d    b e    b u r i e d    a t    a minimum   depth   of   4   feet.   The   ground   lead   must   be   at least   No.   6   AWG   (American   Wire   Gauge)   copper   wire. Change   4 4.2.1/(4-2.2 blank)