Table   2-3.   Troubleshooting   (Cont)
Up
TM-5-6115-584-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Section  III. GENERAL  MAINTENANCE

TM  5-6115-584-34 NAVFAC  P-8-622-34 TO-35C2-3-456-2 Table 2-3. Troubleshooting (Cont) MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION 18. HIGH GENERATOR OUTPUT VOLTAGE (NO LOAD). Step 1. Check  for  voltage  regulator  failure.  Remove  voltage  regulator  lead  (wire  39C16)  from  terminal  17. If voltage goes even higher, the voltage regulator is good. Test  and  repair  defective  regulator  (paragraph  6-6), Step 2. Check  voltage  adjust  rheostat  (R1). Replace  rheostat  (R1)  if  necessary. Step 3. Check  current  voltage  transformer  (CUTI)  (paragraph  6-9b(7)). Replace bad transformer. Step 4. Check  transformer  T2  (paragraph  4-38(  15),  TM  5-6115-584-12). Replace bad transformer. 19. FREQUENCY METER (M3) FAILS TO REGISTER. Step 1. Check  transformers  T1  and  T2  (paragraph  4-38  (14  &  15),  TM  5-6115-584-12). Replace bad transformers. Step 2. Check  frequency  meter  and  transducer  (paragraph  6-4). Replace bad meter or transducer. 20. BATTERIES  DO  NOT  CHARGE. Step 1. Check battery charging alternator stator (paragraph 8-2). Replace bad stator. Step 2. Check battery charging alternator rotor (paragraph 8-2). Replace bad rotor. Step 3. Check  regulator-rectifier  assembly. Replace bad regulator-rectifier. Step 4. Check DC control windings in the CVT (paragraph 6-9). Replace if circuit is open. Change 7   2-11