Figure  4-2.  Grounding  Generator  Set
Up
TM-5-6115-584-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Section V. PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)

TM  5-6115-584-12 NAVFAC  P-8-622-12 TO-35C2-3-456-1 TM-05682C-12 Section  II.  MOVEMENT  TO  A  NEW  WORKSITE 4.3 DISMANTLING  GENERATOR  SET  FOR  MOVE- MENT. a. Preparation  for  Movement. (1)  Disconnect  the  load  cables. (2) Remove exhaust pipe extension if used. (3) Make certain vent on underside of fuel filler cap is closed. (4) Refer to the Items Troop Installed or Authorized List  (Appendix  B  and  make  sure  all  items  are  on  the equipment. (6) On ASK equipped generators, remove batteries access  door.  Disconnect  negative  battery  cable  from battery. (7) Disconnect any other hoses, lines or cables, if used. (8) Close and secure all doors and panels. b.  Movement.  Preferred  means  of  movement  is  to transport. Towing for short distance is permissible if terrain is suitable. 4-4. REINSTALLING GENERATOR SET AFTER MOVE- MENT. (5)Disconnect the ground lead from the ground stud. Refer to paragraph 4-2 for reinstallation after movement to a new worksite. Section   III.   REPAIR   PARTS;   SPECIAL   TOOLS;   SPECIAL   TEST,   MEASUREMENT AND   DIAGNOSTIC   EQUIPMENT   AND   SPECIAL   SUPPORT   EQUIPMENT 4-5.   SPECIAL   TOOLS   AND   EQUIPMENT. 4-6.   MAINTENANCE   REPAIR   PARTS. Special tools are listed in Appendix D, Section Ill. Repair   parts   and   equipment   are   listed   and   illustrated in   the   repair   parts   and   special   tools   list   manual covering   organizational   maintainenace   for   this   Gener- ator   Set. Section   IV.   LUBRICATION   INSTRUCTIONS 4-7.   LUBRICATION. a. Lubrication Order. Lubrication instructions for the Generator Set are contained in L05-6115-564-12. (F)  Air  Force  lubrication  instructions  appear  in  the applicable  work  card  set  in  the  TO  35C2-3-1-428  series. NOTE Insure  that  crankcase  is  hot  before  draining oil. (b)  Oil  Change  (see  figure  3-20).  On  ASK  equipped generators,  remove  oil  access  door. (5)   Open   drain   plug   (1,   figure   4-30)   and   drain oil   filter   oil   into   a   container   having   at   least   a   1 quart   capacity. (6)   Remove   through   bolt   (2)   and   Pull   oil   filter body  (3)  loose  from  oil  filter  adapter  (5). (7)   Discard   gasket   (4)   and   oil   filter   element (6). (8)  Wipe   inside   of   oil   filter   body   (3)   clean   with   a rag. (1)   With   drain   valve   closed,   disconnect   oil   drain hose  from  the  plug  on  the  skid-base. (2)  Open  drain  valve  and  drain  oil  into  a  con- tainer   having   at   least   a   7   quart   capacity. (3)   Close   drain   vaive. (4)  Connect  oil  drain   hose   to   plug   on   skid-base. 4-4 Change   7 (9)   Wipe   inside   of   adapter   (6)   clean   with   a rag.   Insure   the   gasket   groove   is   free   of   foreign material.   Inspect   gaskets   (7)   and   (10)   tO  b e    s u re they   are   not   torn   or   frayed.   Check   that   retainer   (8), and   spring   (9)   are   not   deformed.   Replace   damaged components.