Table  3-2.  Operator/Crew  Preventive  Maintenance  Checks  and  Services  (Cont.)
Up
TM-5-6115-584-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Figure  3-2.  Battery  Assembly

TM  5-6115-584-12 NAVFAC  P-8-622-12 TO-35C2-3-456-1 TM-05682C-12 Table   3-3.   Troubleshooting   (Cont) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION 7.  GENERATOR  SUPPLIES  NO  VOLTAGE  TO  LOAD. Step  1.  Check  main  circuit  breaker  for  ON  position  on  ac  output  control  box. Place  circuit  breaker  in  ON  position.  If  breaker  will  not  stay  on,  perform  the  following actions: Make  certain  load  leads  are  attached  to  the  correct  load  terminals. Make  certain  connections  are  clean  and  tight. Verify  load  is  not  excessive  to  generator  capability  and  does  not  have  an  internal  short. Notify  higher  level  maintenance. 8.  GENERATOR  SUPPLIES  IMPROPER  (UNDER  OR  OVER)  VOLTAGE  FREQUENCY  TO  LOAD. Step   1.   Check   reconnection   switch   on   ac   output   control   box. Make  certain  switch  position  matches  load. Disconnect  load  before  switching. Step   2.   Check   load   terminal   board   (paragraph   3-17). Make  certain  load  leads  are  attached  to  the  correct  load  terminals.  Make  certain connections  are  clean  and  tight. Step   3.   Check   engine   speed. Adjust  engine  speed  by  turning  speed  control  assembly  until  frequency  meter  on control  panel  indicates  60  Hz  with  load  on  Generator  Set. If  engine  speed  cannot  be  brought  up  so  that  Generator  operates  at  60  Hz,  check external  governor  linkage  for  binding  and  check  steps  under  ENGINE  STARTS BUT DOES NOT RUN SMOOTHLY. If  engine  speed  cannot  be  brought  down  so  that  Generator  operates  at  60  Hz,  check external  governor  linkage  for  binding  or  notify  higher  level  maintenance (paragraph   3-21). 3-11. BATTERY  ASSEMBLY. a.  Inspect (see figure 3-2).  On  generators  equipped  with acoustic suppression kit (ASK), remove batteries access door for Inspection. (1) Inspect battery cable terminal connectors (2),  (10) and (11) for corrosion,  deterioration, or physical damage. Inspect battery terminal covers (16) for proper installation and physical condition. Replace if cracked, split or torn.         (2) Inspect cables (l), (3), and (4) for breaks, damage and Section  V.  OPERATOR  MAINTENANCE  PROCEDURES (3) Inspect battery top frames  (5),  bottom  frame  (12), and tray (13) for corrosion or physical damage. Check to see   that   frame   is   held   securely   in   place   and   that   all attaching hardware, nut (7), washer, (8), screw  (14), washer (15), and bolt (9), is securely in place. Check that frame is free of electrolyte. (4) Inspect battery (6) for leaks or cracks. Check top of  battery  and  battery  caps  for  cleanliness.  Check  bat- tery   electrolyte   (liquid)   level.   Level   should   be deteriorated insulation. 3 -8 C h a n g e     7