Table  4-2.  Troubleshooting  (Cont)
Up
TM-5-6115-584-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Table  4-2.  Troubleshooting  (Cont)

TM   5-6115-584-12 NAVFAC  P-8-622-12 TO-35C2-3-456-1 TM-05682C-12 Table   4-2.   Troubleshooting   (Cont) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION 9. ENGINE SHUTS DOWN. Step  1.  Check  oil  level  (paragraph  4-51). Add proper grade of oil. Step  2.  Check  for  restricted  air  cooling  system  (paragraph  4-41). Clean  restrictions  from  system. Step  3.  Check  for  overload  on  generator. Keep  generator  load  within  set  capability. Step  4.  Check  low  oil  pressure  switch  (paragraph  4-31). Replace a bad switch. Step  5.  Check  thermo  over  heat  switch  (paragraph  4-17c). Replace a bad switch. 10.  ENGINE  VIBRATES. Step  1.  Engine  mounts  loose  or  bad  (paragraph  4-52). Tighten  mounting  or  replace  as  necessary. Step  2.  Check  for  loose  blower  wheel. Tighten blower wheel. Step  3.  Check  valve  clearance  (paragraph  4-46). Reset   valve   clearance. 11. LOW GENERATOR OUTPUT VOLTAGE (NO LOAD). Step  1.  Low  engine  speed. Set engine speed to achieve 60 Hz at frequency meter (paragraph 2-4). Step  2.  Check  voltage  adjust  rheostat  (R1)  setting  (paragraph  4-38). Set rheostat (R1) for proper output voltage. 12. HIGH GENERATOR OUTPUT VOLTAGE (NO LOAD). Step  1.  Check  voltage  adjust  rheostat  (R1)  setting  (paragraph  4-38). Set rheostat (R1) for proper output voltage. 13. AC CIRCUIT BREAKER (CB1) WILL NOT CLOSE. Step  1.  Check  for  short  circuit  load. Remove  short  circuit. 4-9