OPERATION OF TACTICAL UTILITY GENERATOR SETS.
Up
TM-5-6115-465-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 30 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Section V. OPERATION UNDER UNUSUAL CONDITIONS

TM 5-6115-465-12
TO 35C2-3-446-1
NAVFAC P-8-625-12
TM 06858B/06858D-12
b. Parallel Operation (Load Transfer). The follow-
(7) Carefully watch the SYNCHRONIZING
LIGHTS of the "on-coming" set. At the instant both
ing method of parallel operation is to be used when it
lights go dark, move the circuit breaker switch of the
is necessary to transfer the load from one set to the
"on-coming" set to the CLOSE position.
other without interrupting power.
(8) Adjust the voltage and frequency rheostats
NOTE
of both sets until load and current are divided equal-
ly between the two generator sets, as explained in
Visually check that the power cable
paragraph 2-13a steps 7 and 8.
and parallel cable are in accordance
with figure 2-5. If the cables are not
(9) Move the circuit breaker switch (30) of the
attached as indicated, shutdown the
"on-line" set to the OPEN position.
"on-line" set and follow instructions
in paragraph 2-12c. Parallel cables
( 1 0 ) Place the operations switch of the "on-
not required with utility generator
coming" set to the SINGLE UNIT OPERATION
sets.
position.
(11) Readjust voltage and frequency of the "on-
CAUTION
coming" set as necessary.
D o not attempt load connects in
(12) Refer to paragraph 2-11 and stop the "on-
paragraph 2-12c unless all sets are off
line" set.
and no other external voltage is ap-
plied to the load.
(1)  The set in operation shall be designated as
"on-line" and sets placed in parallel operations shall
a. General. The diesel engine of a generator set on
be designated "on-coming".
standby service which is normally operated under op-
timum conditions should be exercised at least every
(2) Place the operations switch (26, figure 2-7) on
30 days. However, under any extreme environmental
both sets in the PARALLEL OPERATION position.
c o n d i t i o n , the interval between exercise periods
s h o u l d be shortened appropriately. The exercise
period should be long enough to enable the engine to
CAUTION
attain normal operating temperature.
b . Exercise Procedures.
Do not close the circuit breaker
switch after starting the "on-coming"
(1) Perform the before operation checks and ser-
set as serious damage to one or both
vices of table 3-1.
generator sets may result.
(2) Refer to paragraph 2-10 and start the engine.
(3) Refer to paragraph 2-10 and start the "on-
coming" set. Do not perform steps 7 & 8 of figure 2-8.
(3) After allowing sufficient warm up time, run
the engine at full speed for the period of time required
(4) Note the voltage indicated on the "on-line"
t o obtain two consecutive collant temperature
set. Adjust the voltage of the "on-coming" set to the
readings at a 15 minute interval of 160°F (71°C)
voltage noted on the "on-line" set.
minimum.
(5) Adjust the frequency of the "on-coming" set
(4) Allow the engine to run for an additional 30
to a higher value than that of the "on-line" set.
minutes while performing the during operation checks
and services listed in table 3-1.
(6) Slowly reduce the fre uency of the "on-
coming" set until the SYNCHRONIZING LIGHTS
(25, figure 2-7) flash at 2 to 3 second intervals.
(5) Refer to paragraph 2-11 and stop the engine.
(6) Perform the after operation checks and ser-
vices listed in table 3-1.
CAUTION
(7) Correct any deficiencies note during or after
Do not lace the circuit breaker
operation.
switch of the "on-coming" set in the
C L O S E position while the SYN-
C H R O N I Z I N G LIGHTS are lit as
damage to one or both generator sets
may result.
2-20.2