Current Transformer CT 4 (50/60 Hertz Generator Sets)
Up
TM-5-6115-457-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 100 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Precise Governor System (LEH GOVERNOR)

P-9-TM-457-35 T. O. 35C2-3-442-2
TM-07464A-35
TM 5-6115-457-34
Manufacturing Part Number
00000-4929
Total Turns
47
Rated Voltage
35 VAC
Rated Current
7.4 amperes
Resistance
0.05 ohms ± 20 percent
Frequency
400 hertz
With 35 volts RMS applied exciting current
Excitation Current
is 1.0 amperes RMS maximum
High Potential Rating
2000 volts between winding and core
Temperature Range
-65° F to +155° F
Weight
2 pounds (approx.)
Overall dimensions
5.00 x 4.12 x 3.25 inches (approx.)
(e) Current transformer CT5 and CT6 (50/60 Hertz Generator Sets)
DOD Drawing Number
70-4086
Manufacturer
Consolidated Diesel Electric Company
Old Greenwich, Connecticut
No Load Voltage
60 volts
Current
8 . 0 amperes
Resistance
0.22 ohms
Frequency
50/60 Hertz
Excitation Current
0.90 amperes m aximum
Total Turns
87
Temperature Range
-65° F to + 155° F
Weight
3 pounds (approx.)
Overall dimensions
5.38 x 5.63 x 6.0 inches (approx.)
(f) Current transformer CT7
DOD Drawing Number
70-4085
Manufacturer
Electromagnetic Industries Inc.
C l e a r w a t e r , Florida
1-15

Privacy Statement - Press Release - Copyright Information. - Contact Us