Click here to make tpub.com your Home Page

Page Title: Load Contactor (CB2) (50/60 hertz generator sets)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

Back
Convenience Receptacle Box Assembly
Up
TM-5-6115-457-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 100 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Load Contactor (CB2) (50/60 hertz generator sets) (cont)

P-9-TM-457-35
T.O. 35C2-3-442-2
TM-07464A-35
TM 5-6115-457-34
Voltage Stability:
Short Term (30 seconds)
within bandwidth equal to 1 percent of
Precise Sets
rated voltage.
within bandwidth equal to 2 percent of
Utility Sets
rated voltage.
Long Term (4 hours)
within bandwidth equal to 2 percent of
Precise Sets
rated voltage.
within bandwidth equal to 4 percent of
Utility Sets
rated voltage.
1 percent
Voltage Drift (8 hours)
Transient performance
(application or rejection
of load).
Resumption of steady
state condition :
within 0.5 seconds
Precise Sets
within 3 seconds
Utility Sets
Overshoot and Undershoot:
Precise Sets (50/60 Hertz) 15 percent of rated voltage
12 percent of rated voltage
Precise Sets (400 Hertz)
20 percent of rated voltage
Utility Sets
40 pounds (approx.)
Weight
20.0 x 6.50 x 9.88 inches (approx.)
Overall dimensions
4.
Load Contactor (CB2) (50/60 hertz generator sets)
70-501
DOD Drawing Number
Hartman Electric Manufacturing
Manufacturer
Mansfield, Ohio
HB Electrical Mfg. Co.
Mansfield, Ohio
B-301E (Hartman Electric)
Manufacturer's Part Number
HB200A (HB Electrical)
1-11
Change 4

Privacy Statement - Press Release - Copyright Information. - Contact Us