Click here to make tpub.com your Home Page

Page Title: Permissive Paralleling Relay
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

Back
Overload Relay
Up
TM-5-6115-457-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 100 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
RADIATOR

T.O. 35C2-3-442-2
P-9-TM-457-35
TM 5-6115-457-34
TM-07464A-35
Manufacturer's Part Number 00000-4857
Trips if current in anyplace exceeds 110
Function
percent of rated current on an inverse time
principle.
3 wire, 3 phase 50/60 and 400 Hz 0.75
AC Input (Signal)
ampere per phase (at 100 percent rated load)
28 VDC 0.1 ampere maximum.
DC Input
Operates in a minimum of 8 minutes ±2
Time Delay
minutes after the current in any phase
remains at 130 percent of rated current.
-65° F to +140°F
Temperature Limits
Two contacts, 1 normally open, 1
Contact Arrangement
normally closed
10 ampere resistive or 5 ampere inductive,
Contact Rating
28 VDC
5,000 hour minimum
Service Life
1 pound (approx.)
Weight
3.87 x 2.68 x 3.62 inches (approx.)
Overall dimensions
8. Permissive Paralleling Relay
70-1118
DOD Drawing Number
Electromagnetic Industries Inc.
Manufacturer
C l e a r w a t e r , Florida
23390
Manufacturer's Part Number
24 VDC, 200 milliamperes maximum.
External Power Required
0-20 VAC, 60 to 400 hertz. At 300 VAC,
Input Signal AC Burden
40 milliamperes maximum.
5 and 6 normally closed with AC signal
Contact Operation
above 10 volts.  7 and 8 normally open
with AC signal above 8 ± 1 volt.
28 VDC, 10 amperes resistive, 5 amperes
Contact Rating
inductive.
5,000 hours minimum
Life Expectancy
1 pound (approx.)
Weight
2.56 x 3.38 x 3,00 inches (approx.)
Overall dimensions
1-8 Change 7