Click here to make tpub.com your Home Page

Page Title: Overload Relay
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

Back
Reverse Power Relay
Up
TM-5-6115-457-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 100 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Permissive Paralleling Relay

P-9-TM-457-35 T.O. 35 C2-3-442-2
TM-07464A-35 TM 5-6115 -457-34
6.
Reverse Power Relay
(b) 400 hertz generator sets
76-4194
DOD Drawing Number
Electromagnetic
Manufacturer
Industries, Inc.
C l e a r w a t e r , Florida
Manufacturer's Part Number
63030-240-50 (El. Ind.)
Trips when reverse power into generator
Function
set exceeds 50 percent of rated output.
0-10 VDC with AC signal superimposed on
DC Input Voltage
DC input, 50 volts maximum.
24 VDC across terminals 3 and 4, terminal
External Power
3 is positive.
5 VDC across terminals 1 and 2, terminal
Trip Voltage
1 is positive.  (Corresponds to approximately
50 percent reverse power.)
±0.1 VDC under standard conditions. ±1
Trip Voltage Tolerance
VDC with any combination of superimposed
AC frequency and temperature within
specified limits.
50 to 400 hertz.
Frequency trip effect
Frequency Range
±.4 VDC.
-65° F to +170°F. Temperature trip effect
Temperature Limits
±0.5 volt.
Contacts 5 and 6 normally open.
Contact Arrangement
Contacts 7 and 8 normally closed.
10 amperes resistive, 28 VDC
Contact Rating
Service Life
5,000 hour minimum.
Weight
1 pound (approx.)
3.09 x 3.44 x 2.66 inches (approx.)
Overall dimensions
7. Overload Relay
70-1135
DOD Drawing Number
Manufacturer
Consolidated Diesel Electric Co.
Old Greenwich, Corm.
Change 7 1-7