Short Circuit Relay
Up
TM-5-6115-457-34 Generator Set Diesel Engine Driven Tactical Skid Mtd. 100 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
Reverse Power Relay

P-9-TM-457-35 T.O. 35C2-3-442-2
TM-07464A-35 TM 5-6115-457-34
(b) 400 hertz generator sets
76-4181
DOD Drawing Number
Electromagnetic Industries, Inc.
Manufacturer
Clearwater, Florida
63030-230-50
Manufacturer's Part Number
Trips if generator set output current exceeds
Function
180 ±25 percent of generator set rated current.
10 volts at 60 hertz and 75° F on any phase to
Trip Voltage
neutral
±0.3 volt at 60 hertz and 75°F, ±1.5 volt at any
Trip Voltage Tolerance
combination of frequency and temperature devia-
tion within specified limits.
Frequency Range
50 to 400 hertz. Frequency trip effect ±0.6 volt.
-65° F to +170°F. Temperature trip effect
Temperature Limits
±0.6 volt.
Instantaneous.
operating Time
Contact 5 and 6 normally closed.
Contact Arrangement
Contacts 7 and 8 normally open.
10 amperes resistive, 28 VDC.
Contact Rating
5000 hour minimum.
Service Life
1 pound (approx.).
Weight
3.09 x 3.44 x 2.66 inches (approx.).
Overall Dimensions
1-6A
Change 3