Regulator Checks and Adjustments
Up
TM-5-6115-400-35 Generator Set Diesel Engine Driven 200 KW 60 Cycle AC 120/208V 240/416V 3 Phase Convertible to 167Kw 50 Cycle 120/208V 240/416 V Manual
Next
Figure 13. Wiring for generator regulator checks.

TM 5-6115-400-35
screw.
The  most  convenient
method of performing this operation
is to insert the gage, press the
armature down against it to hold it in
place, and then turn the contact
screw until the contacts barely
touch.
(b) Voltage
Setting-(fig.
Disconnect  battery  cable  from
regulator, and connect voltmeter
between regulator battery terminal,
and ground screws in the end of the
regulator.
With  the  generator
operating at approximately 3,000
RPM and the regulator at operating
temperature,  note  the  voltage
setting.
Adjust by turning the
adjusting screw at the base of the
unit, thereby changing the spiral
spring tension.
Increasing the
spring tension increases the voltage
setting.
After each change of
adjustment,  reduce
generator
speed until cutout relay opens; then
return to speed and read voltage.
(3) Current Regulator.
Two checks and
adjustments are required on the current
regulator: air gap and current setting. The
AIR GAP and not the POINT OPENING is
checked and adjusted-procedure being
the same as for the voltage regulator
above.
Current Setting (fig. 13). To check the
current regulator setting, it is necessary to
keep the voltage regulator from operating
so that the generator output can increase
to the value for which the current
regulator is adjusted, and thus cause the
current regulator to operate.
Three
methods of preventing voltage regulator
operation are available.  Regardless of
the method used, disconnect battery cable
from  the  regulator  and  connect  an
accurate ammeter in series between
these junctions. This meter will measure
the current regulator setting.  The three
methods of preventing voltage regulator
operation are: