LUBRICATION ORDER AND OIL ANALYSIS
Up
LO-5-6115-614-12 Generator Set Diesel Engine Driven Tactical Skid Mtd. 200 Kw. 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Next
The Metric System and Equivalents

TOTAL MAN-HR
TOTAL MAN HR
INTERVAL
MAN-HR
INTERVAL
MAN-HR
8
0.1
300
1.5
100
0.3
KEY
EXPECTED TEMPERATURE
For arctic
operation
Above + 32°F
+ 40 ° to -10°
F
0 ° to -65 °
F
F
refer
(Above 0 ° )
C
(+4°to -23° )
C
(-19 ° to
C
INTERVALS
LUBRICANTS
CAPACITIES
to
-54° )
C
FM 9-207
OE/HDO
OIL Engine
(MIL-L-2104C) Heavy Duty
Intervals
Crankcase and
33 Quarts
given are in
Filters
(31.2 Liters)
hours of
OIL Can Points
OE/HDO 30
OE/HDO 10
OEA
normal
operation.
OEA
OIL, Engine,
(MIL-L-46167) Sub zero
7. Units in standby service should be started once each
NOTES
week in locations where ambient temperature remains
1.
FOR  OPERATION  OF  EQUIPMENT  IN
below 70 deg F [21.1 deg C] and contains a high
PROTRACTED COLD TEMPERATURES BELOW 10°
F
percentage of humidity.  Start engine, bring unit up to
(-23° ).  Remove lubricants prescribed in the key for
C
normal operating temperature and run for approximately
temperatures above -10° (-23° ). Clean parts with dry
F
C
thirty minutes. Check electrical equipment for corrosion
cleaning SOLVENT. Relubricate with lubricants specified
on all relays and switch terminals.  Check controls for
in the key for temperatures 0° to -65° .
F
F
leaks and proper operation.
2. OIL CAN POINTS. Every 100 hours lubricate the door
8. On units in locations where ambient temperature is
hinges, latches, control linkages and all exposed adjusting
normally above 70 deg F [21.1 deg C] perform, starting
threads with OE-HDO.
procedure as above once every two weeks.
3. ENGINE OIL FILTER. Every 300 hours remove oil
Copy of this Lubrication Order will remain with the
filter, install new filter, fill crankcase, operate engine for 5
equipment at all times; instructions contained herein are
minutes, check for leaks, check crankcase oil level and
mandatory.
bring to FULL mark.  The crankcase oil level can be
checked with the engine running or in a static condition.
By Order of the Secretary of the Army:
4. When AOAP Laboratory support is not available, drain
JOHN A WICKHAM
and refill crankcase oil at 300 hours.
General, United States Army
Official:
Chief of Staff
5. Army Oil Analysis Program, (AOAP) may be used to
determine oil change interval on units that have not
R. L. DILWORTH
reached
recommended
operating
hour
change
Brigadier General, United States Army
requirements.
The Adjutant General
6.  Lubricating oil standing in engines that are used
DISTRIBUTION:
infrequently or are in storage between seasons may tend
To be distributed in accordance with DA Form 12-25A,
to oxidize and require changing even though it is not dirty.
Operator and Organizational Maintenance Requirements for
Laboratory testing is the best way to determine whether
Generator Set, Diesel Driven, 120/208V, 240/416V, 100 KW,
oil or fuel is oxidizing under these conditions.
50/60HZ, 3PH, 4 Wire (MEP-008B)
CARD 2 of 2
U.S GOVERNMENT PRINTING OFFICE: 1997 O-418-283 (40480)
PIN: 061758/000