UDC3000 MICROPROCESSOR TEMPERATURE CONTROLLER

TM 5-3895-374-24-1 GP467FB 4. Start the combustion air blower and other related plant equipment. 5. Place  the  CONTROL  MODE  selector  switch  in  the  STACK  position  and  verify  the  setpoint  of  both  temperature controllers 6. If  all  system  limits  are  CLOSED,  the  LIMITS  CLOSED  light  will  come  ON  and  the  purge  timer  will  begin  its  timed delay. 7. Press the LIMITS SET pushbutton to energize the limits hold circuit. NOTE If a momentary break In the limits circuit causes the system to shut down, the LIMITS CLOSED light will come ON again as soon as the limits circuit is again satisfied To aid in troubleshooting, the LIMITS SET light will go OUT and remain OUT.  This indicates that the shutdown was caused by one or more of the switches in the limits circuit rather than by a flame failure. 8. After  the  Purge  timer  has  completed  Its  timed  delay;  purge  latch  relay,  R1,  will  be  energized  and  the  PURGE COMPLETE light will come ON  The Tertiary Air Damper, If applicable, will be released to follow the burner fuel control motor. 9. Verify that the burner control valve Is in the low fire position 10.  Press and HOLD the PILOT pushbutton to start the pilot Ignition sequence. a.  The load relay and safety switch heater of the Honeywell RA890G flame relay will be energized. b.  The Ignition transformer and pilot solenoid valve will be energized. 11.  If a satisfactory flame Is recognized by the UV detector a.  The safety switch heater will be de-energized. b.  Auxiliary Flame relays, R4 & R5, will be energized c.  The purge timer, 1TR, will be de-energized and reset. d.  Alarm Silence relay, R6, will be de-energized, and the flame alarm circuit will be reset. e.  The PILOT ON light will come ON. 12.  Release the PI LOT pushbutton. 13.  If a satisfactory flame is not established within the safety time of the RA890G flame relay: a.  The safety switch heater will continue to heat until it trips. b.  The pilot solenoid and Ignition transformer will be de-energized. c.  The RESET light will come ON.  It will be necessary to open the access door on the front enclosure and reset the flame relay before proceeding CAUTION It  is  recommended  that  power  be  shut  off  before  opening  the  control  panel.    If  the  panel  remains  "hot" while resetting the flame relay, exercise CAUTION to avoid contact with exposed terminals and wiring. (page 3-15)

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing