| |
Back Figure 8-22.—Vane type of water-flow detector. | Up Utilitiesman (Advanced) - Manual for electric, plumbing, water and other utilities | Next Figure 8-24.—OS&Y valve position switch (plunger type). |
Figure 8-23.Fixed pressure water-flow detector with pump.
The electronic pressure drop detector is
often used in sprinkler systems that must
maintain a high excess system pressure over
supply pressure that would delay actuation of
a vane type of water-flow detector. It is
normally mounted to the riser pipe with a
flexible hose connection to the system side
of the check valve. This device requires a
pressure drop of 5 to 20 ounces per square
inch continuing over a period of at least 3 seconds
to signal an alarm. A pressure drop at a slower
rate or of a shorter duration causes no alarm. A
slow pressure drop to 15 psi or less causes a
trouble signal indicating a system leak and low
supply pressure. Pressure increases do not cause
an alarm, but an over pressure condition (200psi)
causes a trouble signal. Trouble signals will also
be initiated when the detectors cover is opened,
supply voltage is outside normal ranges, and an
8-15
internal circuit fails, interfering with detector
function.
Supervisory Alarm Initiating Devices
Supervisory alarm initiating devices cause a
signal at the supervisory control unit and/or
remote receiver when an abnormal fire protection
system condition occurs. In general, supervised
valves are never closed unless a sprinkler system
requires maintenance. Valves that control water
flow to a water-flow detector or valves in a
sprinkler header room or fire pump room that are
normally closed may be supervised. Supervisory
devices for normally open valves signal when the
valve is closed no more than two turns or 20
percent of its total travel. Supervisory devices for
normally closed valves signal when the valve is
|