| |
Back Figure 8-20.—Water spray nozzles. | Up Utilitiesman (Advanced) - Manual for electric, plumbing, water and other utilities | Next Supervisory Alarm Initiating Devices |
valve (alarm check or swing check) that holds
excess pressure on the system side of the check
valve. These detectors are frequently used where a
water surge or hammer causes false alarms with
other types of water-flow detectors. The con-
struction of pressure drop detectors is similar to
the pressure increase detectors. The switch for a
pressure drop detector is arranged to actuate on a
drop in pressure. There is no retarding mechanism
or chamber. A typical switch of this type would be
adjusted for a normal operating pressure in the
range of 50 to 130 psi. The alarm pressure would
be adjustable between 10 to 20 psi below normal
pressure.
A vane type of water-flow detector (fig. 8-22) is
used only in wet pipe sprinkler systems. The
detector is assembled at the pipe by drilling a hole
in the wall of the sprinkler pipe, inserting the vane
into the pipe, then clamping the detector on with
U-bolts. When the sprinkler system is actuated by
fire, the water flowing through the pipe causes the
87.370
Figure 8-22.Vane type of water-flow detector.
vane to move. A mechanical linkage connects the
vane to an adjustable retarding device, usually a
pneumatic dashpot. The retarding device actuates
the alarm switch or switches and/or signal
transmitter. The retarding device setting is usually
in the range of 30 to 45 seconds. A maximum
setting may be as high as 90 seconds if necessary.
The pressure pump/pressure drop type of
water-flow detector is used in large sprinkler
systems and in those systems with inadequate
water pressure to reliably operate one of the other
types of water-flow detectors. These detectors are
also known as fixed-pressure, water-flow detectors,
with pump (fig. 8-23). This detector has a pump,
pump motor, and control unit. It is arranged for
strap-mounting to the sprinkler system riser. The
device provides a water-flow alarm signal, a low
system water pressure supervisory signal, and
excess pressure in the system to prevent surges in
the supply pressure from opening the alarm check
valve and causing operation of the water motor
gong or other alarm indicators.
A typical detector of this type is adjusted to
maintain the system pressure at 25 to 50 psi above
supply pressure. A slow leak at the alarm check
valve or anywhere in the system will cause the
system pressure to drop slowly. When pressure
decreases to 2 psi below the preset value, a
pressure switch closes, causing the pump to start
pumping water from the supply side to the system
side of the alarm check valve at a rate of about 1
gallon per minute (gpm). If the total system leaks
less than 1 gpm, the pressure switch opens and
stops the pump when the preset pressure is
reached. However, if the system leaks are greater
than 1 gpm, system pressure will continue to drop
even with the pump running. If system pressure
decreases to 4 psi below the preset value, a trouble
pressure switch opens to indicate that there is a
leak greater than 1 gpm. If the water pressure
continues to drop to 6 psi below the preset value,
an alarm pressure switch closes, signaling a water-
flow alarm. Some water-flow detectors of this type
have an additional switch that disconnects pump
power when the supply water pressure drops below
14 psi. This prevents pump burnup in case of total
supply shutdown or a break in the supply line.
8-14
|