| |
Back Table 7-6.—Minimum Slope for Sewer Pipe | Up Utilitiesman (Advanced) - Manual for electric, plumbing, water and other utilities | Next Table 7-10.—Capacitiesof Pipe in Gallons Per Minute (Galvanized Iron) |
are easily determined by tracing the layout of the
water supply system as drawn in a print or sketch.
Determining the size pipe you will require to meet
the fixture demand of a facility is more com-
plicated and will be discussed in this section.
Sizing Cold-Water Supply Systems
Some factors that affect the size of the water
service in a plumbing system are the types of flush
device used on the fixtures, the pressure of the
water supply in pounds per square inch (psi), the
length of the pipe in the building, the number and
kind of fixtures installed, and the number of fix-
tures used at any given time. The stream of water
in a pipe is made up of a series of layers moving
at different speeds with the center layer moving
the fastest. The resistance to flow is called pipe
friction and causes a drop in pressure of the water
flowing through the pipe. Friction loss may be
overcome by supplying water at greater pressure
than would normally be required or by increasing
the size of the pipe.
The two most important things to consider are
the maximum fixture demand and the factor of
simultaneous fixture use. The maximum fixture
demand in gallons is the total amount of water
that would be needed to supply all fixtures if they
were being used at the same time for 1 minute.
Since it is very unlikely that all fixtures would be
turned on at the same time, a probable percentage
of the fixtures in use at any given time must be
found. This is the factor of simultaneous use. The
more fixtures in a building, the smaller the
possibility that all will be used at the same time.
Therefore, simultaneous use factors decrease as
the number of fixtures increase.
To estimate the maximum fixture demand in
gallons, the number and type of all fixtures in the
completed plumbing system must be known.
Table 7-8 is used to obtain the maximum fixture
demand. For example, assume a plumbing system
consists of three urinals, two water closets, one
slop sink, two shower stalls, one kitchen sink, one
laundry tray, and four lavatories. From table 7-8
a maximum fixture demand of 321 gallons per
minute (gpm) can be figured. Normally only a
small percentage of fixtures would be used at the
same time, so the maximum fixture demand is
reduced by applying the factor of simultaneous
u s e.
The factor of simultaneous use, also called the
probable demand, is only an estimate. Table 7-9
gives data for making an estimate of probable
demand. When using this table, take the actual
number of fixtures installed, not the fixture unit
value. For example, five fixtures would have a
probable demand of about 50 percent, while 45
fixtures would have a probable demand of about
25 percent. When a table showing the factors of
simultaneous use is not available, a practical way
of figuring the probable demand is 30 percent of
the maximum fixture demand in gallons.
Many factors affect the flow of water through
pipes resulting in a loss of water pressure. Dif-
ficult calculations are required to consider all the
factors involved that may cause a loss of water
pressure. These calculations are beyond the range
of this manual. For simple systems, approximate
figures are acceptable for most plumbing
installations.
Table 7-10 (for galvanized iron pipe) and table
7-11 (for copper tubing) may be used with the
maximum fixture demand and the factor of
simultaneous use to find the correct size of pipe
for water-service lines. The minimum practical
size for a water-service line is 3/4 inch. This size
should be used even when calculations show that
a smaller size could be used.
To continue the example above, the 14 fixtures
would have a factor of simultaneous use of about
35 percent. Since the maximum fixture demand
was 321 gpm, the water-service line must have a
capacity of 35 percent of 321, or 112 gpm. Assum-
ing a length of pipe 60 feet long and a pressure
at the main of 40 psi, table 7-10 or 7-11 shows
that either a 1 1/2-inch galvanized iron or a 1
1/2-inch copper tubing water-service line would
be large enough for the example fixture demand.
Sizing Hot-Water Supply Systems
The hot-water system is that part of the
plumbing installation that heats water and
distributes it to various fixtures. There are many
ways of heating the water, but whichever is used
must be able to supply maximum demand. The
materials used in hot-water systems are similar to
those used in cold-water supply systems. The use
Table 7-9.Factors of Simultaneous Use
7-11
|