| |
Back Overload Protectors | Up Utilitiesman (Advanced) - Manual for electric, plumbing, water and other utilities | Next Hermetic Electrical Schematic Wiring Diagrams |
Figure 14-40.Testing a starting relay with an ohmmeter.
EQUIPMENT AND TEST
PROCEDURES FOR ELECTRICAL
CIRCUIT COMPONENTS
The equipment and procedures for testing
circuit components such as starting relays,
overload protectors, and capacitors are discussed
as follows.
STARTING RELAYS
Starting relays can be tested two ways with an
ohmmeter. The meter can be used to check across
the relay contacts, or it can be used to check across
the relay coil. This does not apply to thermal
relays. Figure 14-40 illustrates procedures for these
tests.
When you check the relay contacts, you must
know if the contacts are normally open or
normally closed. Voltage relay contacts and
thermal relay contacts are normally closed,
whereas current relay contacts are normally open.
The meter reading should indicate continuity
through voltage and thermal relays since the
contacts are normally closed. On the other hand,
if the meter indicates continuity through the
normally open contacts of a current relay, the
contacts are probably fused together.
Another method of checking starting relays
is by using a test line cord and fuse combination
to isolate the relay. Figure 14-41 illustrates the
procedure used in making this test. Obtain a
capacitor of the approximate size used with the
compressor motor. Connect it from the hot side
of the running winding to the hot side of the
starting winding. Connect the test line to the
motor terminals as illustrated in the figure and
plug it in. If the compressor is good it should start
running. After a short time, disconnect the
capacitor. The compressor should continue to
speed up and run normally. This procedure has
accomplished manually what a properly function-
ing starting relay is supposed to accomplish. If
the motor failed to start normally before the
check, the relay is bad.
Voltage and current relay coils can also be
tested for resistance with an ohmmeter. When the
coil is burned out, the meter indicates no
resistance or an open coil. Commercial starting
relay testers are available from several manu-
facturers.
OVERLOAD PROTECTORS
Questionable Klixon external overload protec-
tors should be replaced with new ones. If the
Figure 14-41.Procedures for checking a starting relay with
a test line.
14-24
|