Downloadable Books

   

 


Table  4-1.—Three  Phase  Motor  Controller  Circuit—Continued MANUAL CONDITION ACTION Start button is Current  flows  through pushed the  path  from  L1 through  the  control circuit  fuse,  the  stop button, the start button,   OL1,   OL2, OL3,  and  to  the bottom  of  the  M  coil. L3  is  providing voltage  to  the  top side  of  the  M  coil. The  M  coil  is energized. None When  current energizes   the   M   coil, contacts  M1  through M4   close,   providing current to the three- phase   motor.   (Notice that the start button no  longer  provides  a path  for  current  to flow.)  The  path through  M4  is keeping  the  M  coil energized. Stop  button  is Momentarily,  the  path pushed leading  to  the  M  coil is  open.  This  de- energizes  the  M  coil, and  opens  contacts M1  through  M4. ILLUSTRATION 4 - 10