| |
Back Alternator Test | Up Construction Mechanic Advanced - Construction methods and practices | Next Charging System Insulated Circuit Resistant Test |
connecting the field lead of the tester (fig. 4-10) to
the generator field terminal. Do NOT allow the
vehicle or tester field wires to contact ground. For
the B type of field circuit generator, disconnect the
field wire at the regulator and connect it to the
armature terminal of the regulator. Then start the
vehicle engine and slowly increase speed as you
observe the AMMETER scale for the highest
ammeter reading. When the ammeter reads at the
normal output, test the field lead of the wiring harness
for an open circuit. If the field lead is okay, remove
the regulator for testing, repair, or replacement, as
required. When the ammeter reads at low output or
normal voltage, the generator must be replaced or
repaired. When the ammeter reads at no output or high
voltage and the circuit is not fused at the regulator,
remove the regulator for replacement or repair of its
cutout relay. Also check the regulator ground. If the
regulator is fused, bypass the fuse with a heavy
Figure 4-10.-Generator output test.
jumper and observe the ammeter for output. An output
at this point in your check indicates a blown fuse.
EXCESSIVE OUTPUT TEST
To conduct an excessive output test, set the volt
range knob to the correct voltage range and the volt
lead selector to the EXT VOLTS position. Connect
the black external volts lead to the generator
armature terminal and the red external volts lead to
the generator frame or a good ground. While
observing the VOLTMETER scale for the highest
voltmeter reading, start the engine and slowly
increase its speed. If the voltmeter reads less than
16 volts (12-volt system) or 8 volts (6-volt system),
the current limiter relay of the regulator is the
reason for the high output. If the voltmeter reads
more than 16 volts (12-volt system) or 8 volts
(6-volt system), remove the FIELD wire at the
regulator and observe the AMMETER scale. When
the ammeter reading shows no output, you have a
defective regulator which should be repaired or
replaced. When the ammeter reading indicates a
current flow, remove the field wire at the generator
and observe the ammeter. If the ammeter reading
then shows no output, you have a shorted field
wire. Replace the field wire and connect the
generator to the regulator. On the other hand, if the
ammeter shows that current is flowing, then the
generator has a grounded field.
Another component of the vehicle charging system
you should test is the VOLTAGE REGULATOR. If the
results of the test indicate the voltage is too high or too
low, a faulty regulator voltage limiter or a high-series
resistance in the charging system could be causing the
trouble. Erratic or unstable voltage indicates poor circuit
electrical connections, faulty regulator contacts (burned
or oxidized), or damaged regulator resistors. In any case,
you should proceed with a charging system circuit
resistance test.
CHARGING SYSTEM CIRCUIT
RESISTANCE TEST
The purpose of the charging system circuit
resistance test is to determine the voltage loss between
the output terminal of the generator or alternator and the
insulated battery post, and between the generator or
alternator housing and battery ground post, respectively.
These tests can be run with any voltmeter having a small
scale; that is, 3-5 volts. Any voltage loss caused by high
4-6
|