| |
Back Table 4-2.—Power Factor of Various Types of Electrical Equipment | Up Construction Electrician Intermediate - Electricity handbook for electricians | Next Capacitor Precautions |
however, they also are suitable for operation at
frequencies below 60 Hz. There is no physical limit to
the underfrequency operation of the capacitors. The
limit is economic, in that the capacitor kvar output is
directly proportional to frequency and applied voltage.
If a capacitor is operated at a frequency lower than
rated, its kvar rating is reduced. Since capacitors are
installed in theory to use their rated capacity,
utilization at reduced frequencies is not economical, as
the design rating of the unit can never be achieved.
One method of raising the power factor is to add
capacitors to the circuit, since capacitance is the
opposite of inductance and since too much inductance
is the cause of low power factor. Capacitors are
installed underground on underground distribution
circuits or mounted on poles, as shown in figure 4-27.
The pole-mounted three-phase bank capacitors shown
in figure 4-27 are rated 1,200 kVA capacitance and
13,200Y/7,620 volts; this bank is complete with
switches, fuses, and lightning arresters. The capacitors
can be directly connected to the circuit or switched on
Figure 4-27.Cluster-mounted bank of 4 three-phase
capacitors.
and off as needed. An underground capacitor bank may
be equipped with oil switches for energizing three to
six capacitors. The capacitor equipment may be
installed in a 36-inch diameter vault.
FIXED CAPACITORS.Fixed
capacitor
installations are those that are continuously on the line.
Fixed capacitor banks are connected to the system
through a disconnecting device that is capable of
interrupting the capacitor current, allowing removal of
the capacitors for maintenance purposes. Fixed
capacitor banks should be applied to give a voltage
boost to the system during heavy load periods. Caution
must be used, however, to ensure the boost will not be
excessive during light-load conditions. To isolate or
de-energize a fixed capacitor installation, you should
open the disconnecting switches with rapid positive
action. The successful switching of capacitors
depends, to a considerable extent, on the technique of
the operator and the speed of opening. It is more
difficult to de-energize a capacitor bank than it is to
energize it, because the ease with which capacitor
current is interrupted depends on the point on the
voltage wave when the switch contacts separate. If the
arc is reestablished and maintained with the
disconnecting device open, the switch should be
reclosed at once to avoid damage to the switch.
Another attempt should then be made to open the
disconnecting device. After the disconnecting device
has been opened, the capacitor installation is isolated
but still charged. The capacitors should be left open
from the line for at least 5 minutes before they are
returned to service. This precaution will prevent a
buildup of the line voltage above normal, which may
occur if a fully charged capacitor bank is closed on a
line.
CAPACITOR CONNECTIONS.A typical
three-phase capacitor bank oil switch can be a three-
pole device or three single-pole devices that can be
controlled automatically to switch the bank in or out of
service to control the power factor or to regulate
system voltage. Fuses provide short-circuit protection.
If automatic switching is not required, the fuses can be
used as load-break switches by using a portable load-
break tool.
SWITCHED CAPACITORS. Switched
capacitor installations are those where the capacitor
bank is switched in and out of service, depending upon
system operating conditions. They are usually
switched on when the load requirements are the
greatest and switched off during light-load conditions.
Sometimes the capacitor banks are installed to enable
4-17
|