Figure 4-9.—Three-phase 25 kVA transformers mounted on an H-frame platform.
Up
Construction Electrician Intermediate - Electricity handbook for electricians
Next
Figure 4-13.—Polarity markings and directions of voltages when polarity is subtractive.

portable ground-testing instruments, such as a megger. One procedure for measuring ground resistance with a megger is shown in figure 4-10. If the ground resistance is too high, it may be lowered by one of the following methods: 1.   Drive additional rods. spacing them 6 feet apart, and then connect them in parallel. 2. Use larger rods where low resistance soils are too far below the surface to be reached by ordinary rods. When you are connecting transformers in parallel or in a three-phase bank, it is important to know the polarity of the transformer terminals or leads. In the manufacturing  of  transformers,  the  ends  of  the windings are connected to the leads extending out through  the  case.  The  internal  connection  determines the direction of current flow in the secondary terminal with  respect  to  the  corresponding  primary  terminal. The current may flow in the same direction or in the opposite direction. When the current flows in the primary and secondary windings in the same direction, the polarity of the transformer is said to be subtractive; and when the current flows in the opposite directions, the polarity is said to be additive. Polarity may be further explained as follows: imagine  a  single-phase  transformer  having  two high-voltage and three low-voltage external terminals. Connect  one  high-voltage  terminal  to  the  adjacent  low- voltage terminal, and apply a test voltage across the two high-voltage terminals. If the voltage across the unconnected  high-voltage  and  low-voltage  terminals is less than the test voltage, the polarity is subtractive; if it is greater than the test voltage, the polarity is additive. This test is shown in figure 4-11. Figure 4-11.—Polarity tests. Figure 4-10.—Measuring ground resistance where the ground wire is interconnected with the ground distribution neutral connector. 4-9