| |
Back Troubleshooting and Testing Controllers | Up Construction Electrician Intermediate - Electricity handbook for electricians | Next Combination Starters |
Because there are so many different kinds and makes
of controllers, we will outline a genera! procedure for
locating the source of trouble.
1. If the motor does not start when the main con-
tacts close, the trouble may be as follows:
a.
b.
c.
d.
e.
f.
g.
Open overload heater coil or poor
connection.
Main contacts not making contact. It is not
unusual for one or more contacts to wear to
the degree that they will not make when
closed. This fault will also occur if the
contacts become dirty, gritty, or burned.
Broken, loose, or dirty terminal connection.
Loose or broken pigtail connection.
Open resistance units or open autotrans-
former.
Obstruction of the magnet core, preventing
the contacts from closing.
Mechanical trouble, such as mechanical
interlocks, gummy pivots, and poor spring
tension.
2. If the contacts do not close when the START
button is pressed, the trouble may be as follows:
a.
b. Dirty START button contacts or poor contact.
c.
d.
e.
f.
g.
h.
Open holding coil. This can be tested by con-
necting a voltmeter across the coil terminals
when the START button is pressed. If there
is voltage when the START button is pressed
but the coil does not become energized, the coil
is defective.
Open or dirty STOP button contacts. If more
than one station is connected to the same
controller, each station should be checked. If
FORWARD-REVERSE stations are used
and they are interlocked, check all contacts.
Loose or open terminal connections.
Open overload-relay contacts.
Low voltage.
Shorted coil.
Mechanical trouble.
3. If the contacts open when the START button is
pressed, the trouble may be as follows:
a. Contacts that do not close completely or are
dirty, pitted, or loose.
b. Wrong connection of station to the con-
troller.
4. If a fuse blows when the START button is
pressed, the trouble may be as follows:
a. Grounded circuits.
b. Shorted coil.
c. Shorted contacts.
5. If the magnet is noisy in operation, the trouble
may be as follows:
a. Broken shaded pole causing chattering.
b. Dirty core face.
6. If the magnet coil
trouble may be as follows:
a. . Overvoltage.
is burned or shorted, the
b. Excessive current due to a large magnetic
gap caused by dirt, grit, or mechanical
trouble.
c. Too frequent operation.
TESTING COMPONENT CIRCUITS
The example used here is a control that is operated
by a remote switch, such as a float switch. It is assumed
that the device being controlled (a three-phrase motor)
is in good working order but is not receiving power.
Figure 7-18 shows such a circuit.
The first thing you should check is the line voltage.
To do this check, remove the cover of the control box
and test each line with a voltmeter. You should take the
volt readings between L1 and L2, L2 and L3, and then
between L3 and L1 . If full voltage is found, you should
visually check the power circuit for loose connections.
These terminals include L1, L2, L3, T1, T2, and T3.
Look for signs of heating at these connections. When a
connection becomes loose, the terminal becomes very
hot; and the screw, wire, and terminal become
discolored or charred. Check all terminals and tighten
them if necessary. You should only do this checking
and tightening with the power OFF.
Next, check the control circuitry within the
controller. Do this check by looking at the control
circuit shown in figure 7-18. The external controls, the
magnetic holding coil, and the normally closed
overload contacts are always located between line 1
and line 2. Unless the control has been altered, line 3 is
not part of the control circuit. Check also that the
externally located controlling switches, such as the
7-17
|