Click Here to
Order this information in Print

Click Here to
Order this information on CD-ROM

Click Here to
Download this information in PDF Format

 

Click here to make tpub.com your Home Page

Page Title: Testing Component Circuits
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books

   

 

Back
Troubleshooting and Testing Controllers
Up
Construction Electrician Intermediate - Electricity handbook for electricians
Next
Combination Starters

Because there are so many different kinds and makes of controllers, we will outline a genera! procedure for locating the source of trouble. 1. If the motor does not start when the main con- tacts close, the trouble may be as follows: a. b. c. d. e. f. g. Open   overload   heater   coil   or   poor connection. Main contacts not making contact. It is not unusual for one or more contacts to wear to the degree that they will not make when closed.  This  fault  will  also  occur  if  the contacts become dirty, gritty, or burned. Broken,  loose,  or  dirty  terminal  connection. Loose or broken pigtail connection. Open resistance units or open autotrans- former. Obstruction of the magnet core, preventing the contacts from closing. Mechanical trouble, such as mechanical interlocks, gummy pivots, and poor spring tension. 2. If the contacts do not close when the START button is pressed, the trouble may be as follows: a. b.  Dirty START button contacts or poor contact. c. d. e. f. g. h. Open holding coil. This can be tested by con- necting a voltmeter across the coil terminals when the START button is pressed. If there is voltage when the START button is pressed but the coil does not become energized, the coil is  defective. Open or dirty STOP button contacts. If more than  one  station  is  connected  to  the  same controller, each station should be checked. If FORWARD-REVERSE  stations  are  used and they are interlocked, check all contacts. Loose or open terminal connections. Open overload-relay contacts. Low  voltage. Shorted  coil. Mechanical trouble. 3. If the contacts open when the START button is pressed, the trouble may be as follows: a.   Contacts that do not close completely or are dirty, pitted, or loose. b. Wrong connection of station to the con- troller. 4. If a fuse blows when the START button is pressed, the trouble may be as follows: a. Grounded circuits. b. Shorted coil. c. Shorted contacts. 5. If the magnet is noisy in operation, the trouble may be as follows: a. Broken shaded pole causing chattering. b. Dirty core face. 6. If the magnet coil trouble may be as follows: a. . Overvoltage. is burned or shorted, the b. Excessive current due to a large magnetic gap  caused  by  dirt,  grit,  or  mechanical trouble. c. Too frequent operation. TESTING  COMPONENT  CIRCUITS The example used here is a control that is operated by a remote switch, such as a float switch. It is assumed that the device being controlled (a three-phrase motor) is in good working order but is not receiving power. Figure 7-18 shows such a circuit. The first thing you should check is the line voltage. To do this check, remove the cover of the control box and test each line with a voltmeter. You should take the volt readings between L1 and L2, L2 and L3, and then between L3 and L1 . If full voltage is found, you should visually check the power circuit for loose connections. These terminals include L1, L2, L3, T1, T2, and T3. Look for signs of heating at these connections. When a connection becomes loose, the terminal becomes very hot;  and  the  screw,  wire,  and  terminal  become discolored or charred. Check all terminals and tighten them if necessary. You should only do this checking and tightening with the power OFF. Next,  check  the  control  circuitry  within  the controller. Do this check by looking at the control circuit shown in figure 7-18. The external controls, the magnetic  holding  coil,  and  the  normally  closed overload contacts are always located between line 1 and line 2. Unless the control has been altered, line 3 is not part of the control circuit. Check also that the externally located controlling switches, such as the 7-17

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing