Page Title: Troubleshooting and Testing Controllers
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books

   

 

Back
Figure 7-15.—Two-wire control circuit.
Up
Construction Electrician Intermediate - Electricity handbook for electricians
Next
Testing Component Circuits

LOW-VOLTAGE   CONTROL.—Sometimes   it is desirable to operate push buttons or other control devices at some voltage lower than the motor voltage. in the control system for such a case. a separate source. such as an isolating transformer or an independent voltage supply, provides the power to the control circuit. This independent voltage is separate from the main power supply for the motor. One form of separate control is shown in figure 7-17. When the thermostat calls for cooling and the high-low  pressure  control  is  activated,  the  com- pressor motor starter coil M is energized through the step-down  isolating  transformer.  When  coil  M  is energized,  power  contacts  in  the  240-volt  circuit close  to  start  the  refrigeration  compressor  motor. Since the control circuit is separated from the power circuit  by  the  isolating  control  transformer,  there  is no electrical connection between the two circuits. For this reason, the wire jumper attached to L2 on a starter  should  be  removed  for  different  voltages; however, the overload relay control contact must be included  in  the  separate  control  wiring. TROUBLESHOOTING  AND  TESTING CONTROLLERS In this section it is assumed that the motor and fuse are in good condition. To make certain that the motor is not at fault, connect a voltmeter at the motor terminals and determine whether voltage is available when the contacts of the controller are closed. If there is no voltage, the trouble probably, lies in the controller. Figure   7-17.—Low-voltage   control   circuit. 7-16 TROUBLESHOOTING By   using   a   snap-around   type   of   voltmeter- ohmmeter  or  individual  instruments,  you  can  conduct many of the tests needed to determine opens, shorts, grounds. and continuity in just a short time. You can test malfunctioning circuits for shorted coils; open coils;   grounded   coils;   open   resistances;   shorted resistances; low voltages; high voltages: excessive amperes; broken, loose, or dirty connections; and many other problems with comparative ease. This testing is true of all motors. as well as starters. You should follow a systematic procedure when troubleshooting  controls. WARNING You must exercise extreme caution when test- ing live components. Always use the one-hand rule to avoid completing the circuit between the live component and a metal sur-face. Always have a second person standing by when work- ing on energized equipment and ensure the person is qualified in CPR. When working on anything that should have the power off, always shut the power off yourself. Most disconnects have allowances for a padlock to be used to keep the power from being turned back on. This safety precaution is called “LOCKOUT.” The NAVOSH  Manual,  OPNAVINST  5  100.23, provides  guidance  on  the  Lockout/Tag  out  pro- gram at shore activi-ties according to OSHA regulations. It is extremely important to take this precaution. Controls with voltage over 240 volts should never be energized when you are troubleshooting.