Click Here to
Order this information in Print

Click Here to
Order this information on CD-ROM

Click Here to
Download this information in PDF Format

 

Click here to make tpub.com your Home Page

Page Title: Stopping Generator Set Operation
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books

   

 

Back
Paralleling Procedures
Up
Construction Electrician Basic - Electricity handbook for electricians
Next
Stopping Generator Set Operation, Continued

5. Start the incoming set. The on-line set should be in operation already. 6. After a 5-minute warmup, try the VOLTAGE ADJUST control on the incoming set until the output voltages of both sets are equal. CAUTION If the synchronizing lights do not blink on and  off  in  unison,  the  phase  sequence  is incorrect. Shut  down  the  incoming  set  and recheck the cabling to and from the incoming set. 7. On the incoming set, position the ENGINE M A N U A L    S P E E D    C O N T R O L    u n t i l    t h e SYNCHRONIZING LIGHTS blink on and off as slowly as possible. 8.   With one hand on the CKT BRK switch, adjust the ENGINE MANUAL SPEED CONTROL vernier knob  until  the  SYNCHRONIZING  LIGHTS  dim gradually from full on to full off as slowly as possible. Just as the SYNCHRONIZING LIGHTS dim to out, set and hold the CKT BRK switch to close. When the CKT BRK indicator light comes on, release the switch. 9. On both sets, check that the readings of the PERCENT   RATED   CURRENT   meters   and KILOWATTS  meters  are  well  within  20  percent  of each  other.   If not, increase the engine power of the set with  the  lower  readings  (by  adjusting  the  ENGINE MANUAL SPEED CONTROL to increase the speed) until the readings are about equal. NOTE: The division of the kilowatt load is also dependent on the frequency droop of the two sets and must  be  adjusted  at  the  next  higher  level  of maintenance. If the current does not divide as described above, adjust the reactive current-sharing control located at the right side of the special relay box for equal reading on both percent rated current meters. 10. On the incoming set, readjust the voltage and frequency of the output until it is equal to the output of the on-line set. Removing a Generator Set from Parallel Operation Refer to figure 3-19 while following the procedure for removing a generator set from parallel operation. 3-26 CAUTION Before removing the generator set(s) from parallel operation, make sure the load does not exceed the full-load rating of the generator set(s) remaining on the line. 1.   On the outgoing set, position and hold the CKT BRK switch to OPEN until the CKT BRK indicator light goes out. Release the switch. 2.   On the outgoing set, allow the engine to operate with no load for about 5 minutes. 3. On the outgoing set, pull the DC CONTROL CIRCUIT BREAKER to OFF. 4. On the outgoing set, set the START-STOP- RUN switch to STOP. WARNING Make certain the outgoing set is shut down and there are no voltages at the switchgear terminals connected to the outgoing set. Do not take anybody’s word for it! Check it out for yourself! 5. Disconnect the cables going from the outgoing set to the load switchgear. Stopping Generator Set Operation Refer to figure 3-19 as you study this section. 1. Set the CKT BRK switch to OPEN until the CKT BRK indicator light goes out, then release the CKT BRK switch. 2. Allow the engine to cool down by operating at no load for 5 minutes. 3. Set the START-STOP-RUN switch to STOP. 4. Close all generator doors. MAINTENANCE There  are  actually  three  major  categories  (or  levels) of maintenance. The three categories are (1) depot, (2) intermediate, and (3) organizational. In depot or intermediate  maintenance,  equipment  is  restored  to like-new condition or subjected to some degree to detailed  repairs.  Under  the  organizational  category, generator maintenance may consist of inspection, testing, adjustment, and so forth, and then perhaps

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing