| |
Back Inspection of the Generator | Up Construction Electrician Basic - Electricity handbook for electricians | Next Figure 3-13.—Portable power distribution panelboard. |
OVERCURRENT PROTECTION
If the load cables come into contact with each other
and short-circuit the generator, the generator windings
could be damaged by excessive current unless the
generator windings and load cables are protected by a
circuit breaker. The circuit breaker "breaks" or
interrupts the circuit anytime there is a short circuit or
overload condition in the load cables.
One large load, consuming an amount of power at
or near the maximum power output of the generator,
could theoretically overload the generator in the event
of a fault. In this case, one circuit breaker could trip the
circuit and protect both the generator and the load. But
small-load conductors connected directly to the larger
generator load cables could likely burn up without
drawing enough current to cause the circuit breaker of
the generator set to open the circuit.
In the interest of safe operation of load circuit
conductors and safety of area personnel, you must use
properly sized overcurrent devices (circuit breakers or
fuses).
DISTRIBUTION
The generator load cables are terminated at a type of
distribution bus bar from which one or more
overcurrent protective devices are connected. Current
through each of the overcurrent devices is limited by the
overcurrent rating or setting of the device. In this way
power from the generator may be safely distributed
through protected conductors to the various connected
loads.
PANELBOARDS
A panelboard includes buses and automatic
overcurrent protective devices placed in a cabinet or
cutout box and mounted in (flush) or against (surface) a
wall or partition. The panelboard is accessible only
from the front. A panelboard serves the purpose
mentioned above for the distribution of electric
power.
PHASE RELATIONSHIP
When you connect the generator load to the
panelboard, be careful to match the cable markings to
the panelboard terminals. The same phase relationship
should be maintained throughout the wiring system
from the generator to the load. You may see terminals
marked with numbers, such as L1, L2, L3, and L0
(fig. 3-12, view A) or the letters and symbols A0, B0,
C0, and N (fig. 3-12, view B). Wire in different parts of
the system may be marked with numbered, lettered, or
colored tape. (The color sequence is black, red, blue,
and white.) Either way, the phase sequence is the same.
You may have to "ring out" (identify) unmarked
cables or conductors in the conduit (fig. 3-12, view C)
before connecting them to the power source or load.
This identification process can be accomplished in any
one of several ways. You may use a bell and battery,
buzzer and battery, or ohmmeter, for example. Any of
these devices may be used to check for continuity
through each conductor to ground (a conduit, for
example). After a conductor is identified, it is then
marked.
PORTABLE POWER DISTRIBUTION
PANELBOARDS
Portable, weatherproof, power distribution
panelboards are available, similar to the one shown in
Figure 3-12.Conductor identification.
3-15
|