| |
Back Figure 5-66.—Panelboard connections without excess wire. | Up Construction Electrician Basic - Electricity handbook for electricians | Next Figure 5-68.—Load balancing. |
Load Balancing
Now that you have installed the branch circuit
conductors and breakers, you must balance the load.
Conductors cannot be connected to a panelboard by
attaching each one as you come to it. The arrangement
or sequence of attaching conductors to the panelboard is
determined by the arrangement of the bus bars in the
panelboard, whether the circuits are 240 volts or 120
volts, and the need to balance the load on the phase
conductors. Bus bars are installed into panelboards in
one of several ways. Most of the time, the bus bars are
run in a vertical configuration. In one arrangement, a
split-bus panelboard is used that has all the 240-volt
circuits in the upper section and the 120-volt circuits in a
lower section. Another type of split-bus panelboard
uses one main circuit breaker to feed one set of branch
circuits and a second main circuit breaker to feed a
second set. In many cases, panelboards are designed so
that any two adjacent terminals can be used to provide
240-volt service. This arrangement also means that two
120-volt circuits attached to adjacent terminals are
connected to different phase conductors. Since there
are so many panelboard layouts, you must look at the
panelboard to see how it is set up for 240-volt service,
and you must be sure you get the conductors for 240-
volt circuits connected to the proper terminals.
5-36
Loads that are connected to a panelboard should be
divided as evenly as possible between the supply
conductors. This process of equalizing the load is
commonly referred to as load balancing. The purpose of
load balancing is to reduce voltage drop that results
from overloading one side of the incoming service. It
also prevents the possibility of overloading the neutral.
A perfectly balanced load between the supply
conductors reduces current flow in the neutral to zero.
Load balancing is no problem for 240-volt circuits
on a three-wire, single-phase system since the load has
to be equal on each phase conductor. However, the 120-
volt circuits are a different matter. These must be
connected in such a way that the loads tend to equalize.
Generally speaking, the simplest way to balance the
load on a panelboard is to connect an equal number of
branch circuits to each phase conductor. But this
method does not necessarily give you a balanced load as
will be evident if you will look at the top of figure 5-68.
As you can see, the indiscriminate connection of branch
circuits without consideration of their loads can cause
you to end up with an unbalanced condition. On the
other hand, you can connect the circuits so that one with
a heavy load is offset by one with a light load, which
does result in the balanced condition shown in the
bottom of figure 5-68. Most of the time, you should be
able to connect half of the lighting circuits and half of
the appliance circuits to each phase conductor to give
you a reasonably well-balanced load. Spare circuits
should also be equalized There is one more thing to
consider: When there are appliance circuits where the
loads are known to be heavy, these circuits must be
divided between the phase conductors.
TROUBLESHOOTING
AND REPAIR OF INTERIOR WIRING
SYSTEMS
Electrical troubleshooting is an important part of
your job. Your ability to find a faulty condition quickly
can play an important part in shortening the downtime
caused by failure. To find faulty conditions in circuits,
you must do some inspecting, some calculating, and
some instrument testing. A few moments spent
studying the circuit diagrams before you start actual
troubleshooting will simplify the task of isolating the
trouble. If a circuit fails to function, use logic when you
check for the fault. The trial-and-error method of
finding faults in circuits is inefficient and time-
consuming.
The first step to take in troubleshooting circuits is to
inspect the circuit visually. Check for loose
connections, loose wires, abraded wires, and loose
fittings. An overloaded circuit is a serious problem.
Many times the electrical demand on a circuit is so great
that the circuit fuses blow or the circuit breakers trip. In
some cases, the wrong fuses or circuit breakers are used,
and the wires overheat and burn off the insulation. This
condition causes shorts and grounds and sets up
potential fire hazards.
OPEN, SHORTED, AND GROUNDED
CIRCUITS
An OPEN CIRCUIT occurs in a wiring system
when one or more conductors in a circuit are broken or
otherwise separated. An open circuit is determined by
the failure of a part or all of an electrical circuit to
operate, even though the fuses may not be blown. Use
the following maintenance procedures for locating the
source of the trouble:
1. Initially, you should make a visual check for a
broken or loose connection at the first dead
(nonoperating) outlet in the circuit. If a defective
connection is found, tighten or repair the connection.
|