Click Here to
Order this information in Print

Click Here to
Order this information on CD-ROM

Click Here to
Download this information in PDF Format

 

Click here to make tpub.com your Home Page

Page Title: Troubleshooting and Repair of Interior Wiring Systems
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books

   

 

Back
Figure 5-66.—Panelboard connections without excess wire.
Up
Construction Electrician Basic - Electricity handbook for electricians
Next
Figure 5-68.—Load balancing.

Load  Balancing Now that you have installed the branch circuit conductors and breakers, you must balance the load. Conductors  cannot  be  connected  to  a  panelboard  by attaching each one as you come to it. The arrangement or sequence of attaching conductors to the panelboard is determined by the arrangement of the bus bars in the panelboard, whether the circuits are 240 volts or 120 volts, and the need to balance the load on the phase conductors. Bus bars are installed into panelboards in one of several ways. Most of the time, the bus bars are run in a vertical configuration. In one arrangement, a split-bus panelboard is used that has all the 240-volt circuits in the upper section and the 120-volt circuits in a lower  section.  Another  type  of  split-bus  panelboard uses one main circuit breaker to feed one set of branch circuits and a second main circuit breaker to feed a second set. In many cases, panelboards are designed so that any two adjacent terminals can be used to provide 240-volt  service.  This  arrangement  also  means  that  two 120-volt  circuits  attached  to  adjacent  terminals  are connected to different phase conductors. Since there are so many panelboard layouts, you must look at the panelboard to see how it is set up for 240-volt service, and you must be sure you get the conductors for 240- volt circuits connected to the proper terminals. 5-36 Loads that are connected to a panelboard should be divided as evenly as possible between the supply conductors. This process of equalizing the load is commonly referred to as load balancing. The purpose of load balancing is to reduce voltage drop that results from overloading one side of the incoming service. It also  prevents  the  possibility  of  overloading  the  neutral. A   perfectly   balanced   load   between   the   supply conductors reduces current flow in the neutral to zero. Load balancing is no problem for 240-volt circuits on a three-wire, single-phase system since the load has to be equal on each phase conductor. However, the 120- volt circuits are a different matter. These must be connected in such a way that the loads tend to equalize. Generally speaking, the simplest way to balance the load on a panelboard is to connect an equal number of branch circuits to each phase conductor. But this method does not necessarily give you a balanced load as will be evident if you will look at the top of figure 5-68. As you can see, the indiscriminate connection of branch circuits without consideration of their loads can cause you to end up with an unbalanced condition. On the other hand, you can connect the circuits so that one with a heavy load is offset by one with a light load, which does result in the balanced condition shown in the bottom of figure 5-68. Most of the time, you should be able to connect half of the lighting circuits and half of the appliance circuits to each phase conductor to give you  a  reasonably  well-balanced  load.  Spare  circuits should also be equalized There is one more thing to consider: When there are appliance circuits where the loads are known to be heavy, these circuits must be divided between the phase conductors. TROUBLESHOOTING AND REPAIR OF INTERIOR WIRING SYSTEMS Electrical troubleshooting is an important part of your job. Your ability to find a faulty condition quickly can play an important part in shortening the downtime caused by failure. To find faulty conditions in circuits, you must do some inspecting, some calculating, and some  instrument  testing.  A  few  moments  spent studying the circuit diagrams before you start actual troubleshooting will simplify the task of isolating the trouble. If a circuit fails to function, use logic when you check  for  the  fault.  The  trial-and-error  method  of finding  faults  in  circuits  is  inefficient  and  time- consuming. The first step to take in troubleshooting circuits is to inspect   the   circuit   visually.   Check   for   loose connections, loose wires, abraded wires, and loose fittings.  An  overloaded  circuit  is  a  serious  problem. Many times the electrical demand on a circuit is so great that the circuit fuses blow or the circuit breakers trip. In some cases, the wrong fuses or circuit breakers are used, and the wires overheat and burn off the insulation. This condition  causes  shorts  and  grounds  and  sets  up potential fire hazards. OPEN, SHORTED, AND GROUNDED CIRCUITS An OPEN CIRCUIT occurs in a wiring system when one or more conductors in a circuit are broken or otherwise separated. An open circuit is determined by the failure of a part or all of an electrical circuit to operate, even though the fuses may not be blown. Use the following maintenance procedures for locating the source of the trouble: 1. Initially, you should make a visual check for a broken   or   loose   connection   at   the   first   dead (nonoperating) outlet in the circuit. If a defective connection is found, tighten or repair the connection.

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing