TM  55-1520-240-23-7 8-2 TEST POWER  TURBINE  INLET TEMPERATURE (PTIT) INDICATOR (Continued) 8-2 POSITION ERROR TEST 11. Adjust tester (2) cause  indicator (1) to  read  600ºC with  indicator dial in  normal (vertical) position. 12. Rotate  indicator  (1) 90º  counterclockwise.   Tap indicator and  record  reading.  Return  indicator  to original  position. 13. Rotate  indicator (1) 90º  clockwise.  Tap  indicator and  record  reading.  Return  indicator to  original position. 14. Rotate  indicator  up  (dial  in  horizontal  position). Tap  indicator  and  record  reading.   Return indicator  to  original  position. 15. Compare readings from steps 11, 12, 13, and  14. Difference  shall  not be  more  than  24ºC. GROUNDED  THERMOCOUPLE  TEST 16. Adjust  tester (2)  to  800ºC.  Check  indicator. Indicator (1) shall  read  795ºC  to 805ºC.  Record indicator  reading. 17. Ground  tester (2) chromel lead  (4) to indicator (1) case.   Check indicator.   Indicator  shall  not  read more  than  5ºC from  reading  in  step  16. 18. Remove  ground  from  chromel lead. 19. Repeat  steps 17  and  18, grounding  tester alumel lead  (5)  to  indicator (1)  case.   Check indicator. Indicator  shall  not  read  more  than  ±5ºC from reading  in  step  16. 8-18