Figure 1-3.  CD800/830 and CD802/832 Combustible Gas Detector Models
Up
TM-10-6665-297-13P Bacharach Combustibles Gas Alarm System NSN 6665-00-410-4982 Manual
Next
CONTROL MODULE CIRCUITRY

TM 10-6665-297-13&P 1-2 GAS DETECTOR UNITS (continued) 1-2.3 Detector Models  (continued) (3)   Model 23-4017: remote mounting detector housing with integral air aspirator for continuous sample drawing.  Sample gas is transported to the sensor through a length of tubing from enclosed areas, tanks,  and  vessels  not  otherwise  readily  accessible;  from  high-velocity  gas  streams;  from  areas containing   more   dirt   or   moisture   than   desirable   for   diffusion   sampling;   from   nitrogen-inerted atmospheres where air blending is required; from elevated-temperature areas (200°  F or higher); or any  situation  where  sample  conditioning  is  required.    (For  example:  If  flash  point  of  combustible material  is  greater  than  70°   F,  sample  line  and  detector  must  be  heated  to  above  flash  point.) Approved for use in N.E.C.  Class I, Division 1, Groups A, B, C, and D hazardous areas. (4)  Model  800-086:  explosion-proof,  weatherproof  detector  housing;  diffusion  sampling  (Figure  1-3). Approved for use in N.E.C.  Class I, Division 1, Groups B, C, and D hazardous areas. (5) Model 23-7317: explosion-proof, weatherproof housing; diffusion sampling; high-humidity shield to protect sensor element from heavy moisture content in the air (Figure 1-3).  Approved for use in N.E.C.  Class I, Division 1, Groups B, C, and D hazardous areas. Catalytic sensor elements in all models have flame arrestors caps to prevent ignition of combustible gases in the  air.    Each  detector  assembly  has  a  5-layer  mesh  monel  screen  enclosing  the  plug-in  sensing  element, providing redundant flame-arresting protection. 1-3 CONTROL MODULES All CD800/830 and 802/832 control modules contain power regulating and signal processing circuitry, percent L. E.L.  indicating meter, indicator lights to signal gas conditions and system operating modes, circuit adjusters, and relays in small, compact units. CD800/830   series   and   CD802/832   series   control   modules   differ   in   that   each   CD800/830   control   module ordinarily monitors a single detector (or if two, the signals from both are summed as if for one), whereas each CD802/832 control module incorporates two discrete channels for the independent monitoring of signals from two  detectors.    The  CD802/832  control  module  features  a  channel  selector  control  that  can  be  set  either  to AUTO  (automatic  mode),  in  which  meter  and  signal  lights  respond  to  the  channel  receiving  the  strongest signals from the detectors, or to either of two channel positions, in which meter and signal lights respond to the channel   selected.      Alarm,   warning,   and   failure   circuitry   and   indicators   remain   active   for   both   channels, regardless of the channel-selector control position. 23-9617 7-1-76 1-6

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing