Chapter 5. DIRECT SUPPORT MAINTENANCE
Up
TM-5-6130-301-13-P Battery Charger Distribution Panel (MIL-P-52457) Manual
Next
Figure 5-1. Panel (Sheet 2 of 2)



TM5-6130-301-13&P
(2) Meters voltmerer-ohmmeter.
(a) Loosen panel fastener screw (1) and open panel (2).
(b) Remove power leads from meter (3) and remove screws and attaching hardware from meter.
(c) Remove meters from panel.
(3) Circuit breaker (8 amp top row).
Loosen panel fastener screws (1) and open panel (2).
(a)
(b)
Remove screws, nuts, hardware from bus bar supports (4) and remove bus bars.
(c)
Remove nuts and washers connecting bus bars (5) to circuit breakers, 8 amp (6).
(d)
Remove bus bar connectors (7).
(e)
Remove screw and nut attaching bus bar jumper (8) from bus bars (5) and remove bus bar jumper
(f)
Remove circuit breaker power lead.
1.
Panel Fasteners Screw
13.
Receptacle
7.
Bus Bar Connectors
2.
Panel
8.
Bus Bar Jumper
14.
Diode
Meter
15.
Relay, 200 Amp
3.
9.
Circuit Breaker Boot
4.
Bus Bar Supports
10.
Attaching Hardware
16.
Toggle Switch
5.
Bus Bar
11.
Bus Bar Ground
17.
Control Knob
6.
Circuit Breakers
12.
Circuit Breaker, 20 Amp
18.
Resistor
Figure 5-1. Panel (Sheet 1 of 2)
5-2
Change 4