Table 4-1. Organizational Troubleshooting
Up
TM-5-6130-301-13-P Battery Charger Distribution Panel (MIL-P-52457) Manual
Next
Section IV. MAINTENANCE PROCEDURES



TM5-6130-301-13&P
Table 4-1. Organization Troubleshooting (Continued)
PROBABLE CAUSE
CORRECTIVE ACTION
3. UNCONTROLLED STATION DOES NOT CHARGE BATTERY.
Circuit breaker faulty.
Replace circuit breaker.
Diode open.
Check with ohmmeter.
Replace diode.
Receptacle assembly faulty.
Step 1. Visually check for faulty contacts.
Replace receptacle assembly.
Step 2. Check with voltmeter.
Replace receptacle assembly.
4. AMMETER READS HIGH OR ALL BATTERIES BOIL ON UNCONTROLLED STATION.
Input voltage too high.
If this occurs at all stations reduce input voltage.
5. CURRENT CONTROL FAILS TO CONTROL VOLTAGE.
Rheostat shorted.
Clean or replace rheostat.
6. POWER SWITCH WILL NOT CUT POWER.
Relay sticking closed.
Replace relay.
Switch sticking closed.
Replace switch.
7. METER READINGS SHOW SAME AT ALL POSTIONS (WHEN ALL IN USE).
Shorted diode.
Check diode.
4-4